Permit Information
Permit NumberELE06-01100
StatusFinaled
Name ELCOR ELECTRIC
Site Address 9096 W DALTON PL
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Electrical Rough in
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/7/20066/7/20066/7/2006PPASS
DetailsBob Reichert
nick ###-#### ok to final
Rough-In Permanent Service4/3/20064/3/20064/3/2006PPASS
DetailsBob Reichert
Re-inspection request. Thanks; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen should check refrigerator recpt box, rest corr made, ric ok, p/s u/g n ok
Rough-In Permanent Service3/30/20063/31/20063/31/2006AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called left message, BCC all make-up shall be done, 210.52 (A)(2) receptacles shall be added in any wall space over 2' in width, 110.12(C) there shall be no broken boxes, 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 725.55(A) class 2&3 cables shall not be run with class 1 conductors