Permit NumberELE06-01141
StatusExpired
Name R M E INC
Site Address 5501 W CRUZEN ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Alteration: UPGRADE FUSE BOX ON HOUSE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent Service4/18/20064/19/20064/19/2006AFAIL
DetailsJack Frank
Internet Inspection Request from: Tyler Bowen corrections not made and new violations created, 110.26(F)(2) remove bush for p/s clearence, 110.12(A) seal all unused KOs, 240.24(A) breaker spaces over 6ft7" 408.4 label panel, 314.16 box fill new jbox in basement under stairs, 250.104(A)(1) bond hot and cold called fee due posted also
Permanent Service4/17/20064/17/20064/17/2006PFAIL
DetailsJack Frank
toby Internet Inspection Request from: Tyler Bowen corr. not made and not ready
Final4/14/20064/17/20064/17/2006AFAIL
DetailsJack Frank
###-#### - toby corr. called 250.8 no sms, 312.5 needs conn for all cables and conductors, 310.15 derate at 50%, 250.52&104 grd within 5 ft of u/g pipe, bond hot and cold.110.26(F)(2) remove bush in front of p/s, 240.24 highest breaker position over 6ft7", 250.64(C) no splice allowed in GEC also remove it from raceway and jbox shall not ID 6 or smaller grds and neuts, cow
Conference4/4/20064/4/20064/4/2006PDONE
DetailsWilliam E Thomas
CALL MIKE DELACY BEFORE HEADING TO SITE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
talked about working clearences for panels