Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-01493
StatusFinaled
Name TRINITY MAINTENCE & ELECTRIC
Site Address 3821 W HILLCREST DR
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: wire new addition rewire part of existing house. replace service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/21/20067/21/20067/21/2006APASS
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: joe wheeler ok final
Rough-In Permanent Service5/10/20065/11/20065/11/2006APART
DetailsPat Lass
callfor access house may be locked; Phone #: ###-#### Internet Inspection Request from: joe wheeler
guy is to be within 30 in of weatherhead and use plastic romex connectors on GEC
R/I Ok
Rough-In Permanent Service5/10/20065/10/20065/10/2006AFAIL
DetailsJack Frank
call for access; Phone #: ###-#### Internet Inspection Request from: joe wheeler corr. 312.5 needs conn. for GEC,310.8(D) sunlight resistant wire for mast 230.54(C) wheaterhead shall be above service drop atachment as code noted states, 230.24(B)(1) needs 10ft from grade to drip loop,250.148 shall have all metal boxes grded at time of r/i request, 314.16 box fill outside back recept, 314.17(A&B) needs conn or clamps at all metal boxes