DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/10/20077/11/20077/11/2007PFAIL
DetailsPat Lass
melissa Phone #: ###-####
AFCI breaker trips and doesn't control the bedroom.
Final12/27/200612/28/200612/28/2006PFAIL
DetailsBob Reichert
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not done, needs to install afci and strap gounding electrode conductor to house, rest ok
Final8/2/20068/3/20068/3/2006AFAIL
DetailsBob Reichert
jeff- call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 408.4 complete and definitive circuit directory shall be provided in panels and identify smoke detector circuit, 210.12(B) arc-fault circuit interruptor shall be installed for bedroom, 110.3 panelboard deadfront screw shall be installed,230.28 service mast shall have guy kit installed
Electrical Rough-In6/21/20066/22/20066/22/2006APASS
DetailsJim Schmer
melissa ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
Electrical Rough-In6/21/20066/21/20066/21/2006PFAIL
DetailsJack Frank
melissa; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr. all violations not corrected new ones created, 300.4 nail plates and 11/4", 300.14 6" free length, 110.14(B) shall use devices to splices cannot just twist them, new violation 314.17(C) and 334.30 secure cables within 8" of boxes, Jim S is at site too talk to owner about corrections job still needs r/i for other bath rm afci for bed rm circuits, guy for mast, grd pigtails for switches
Electrical Rough-In6/20/20066/20/20066/20/2006PFAIL
DetailsJack Frank
Melissa; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. met owner 300.14 shall provide 6" free conductor short grd wires,, 300.4(A)(1)(D) nail plates and 11/4",250.148 splice all equip grds #14⽎.14(B) use device to splice all equip grds they are just twisted, 310.16 shall not use #14 switch legs and travelers on 20 amp circuit
Electrical Rough-In6/15/20066/15/20066/15/2006PCANC
DetailsJack Frank
###-#### - melissa see added conference
Conference6/15/20066/15/20066/15/2006PDONE
DetailsJack Frank
###-#### - melissa ok
Rough-In Permanent Service5/25/20065/26/20065/26/2006APASS
DetailsJack Frank
1st in am for electrode ok p/s o/h rec. ok
Electrical Rough-In5/25/20065/25/20065/25/2006PPART
DetailsJack Frank
melissa bierman ###-#### conference only