Permit Information
Permit NumberELE06-01970
StatusFinaled
Name DIAMOND ELECTRICAL SERVICE
Site Address 5450 W GOWEN RD
Project Name 
Customer Number 
ePlanReview 
Description
New overhead service - $4,100 ///Final cert of value is $4,675//9/28/06 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/21/20068/22/20068/22/2006APASS
DetailsJack Frank
ron - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
Final8/16/20068/17/20068/17/2006PFAIL
DetailsJack Frank
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see added r/i note only r/i inspections ever called in are for concrete encased electrode and u/g
Electrical Rough-In8/17/20068/17/20068/17/2006PFAIL
DetailsJack Frank
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called
r/i inspection added 312.5 connector for GEC new building, old small building B C C no violations retained, 200.6 shall have required color for neutral, shall not ID 6 or smaller, 250.32 shall prvide made electrode, grd or bond water system if there, 225.31,32,36, 110.3(B), 408.34(A) shall provide service suitible for service equip as manufactures instructions state, note needs main breaker because it is not a power panelboard per manufactures instruction it is a lighting panelboard
Electrical Rough-In8/11/20068/14/20068/14/2006APART
DetailsJack Frank
RON nOTE: TRENCH; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g ok
Electrical Rough-In8/1/20068/1/20068/1/2006PFAIL
DetailsJack Frank
ron - trench ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
corr and don cover posted called 300.5 (F) needs bedding for u/g too many large rocks and paving material
Electrical Rough-In6/5/20066/6/20066/6/2006APART
DetailsJack Frank
slab inspection//ron wymer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles inspection for electrode only