Permit NumberELE06-02003
StatusFinaled
Name R M E INC
Site Address 8363 W FRANKLIN RD
Project Name 
Customer Number 
ePlanReview 
Description
Install new 100 amp meter & feed for irrigation pump - $3,345
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/8/20066/8/20066/8/2006PPASS
DetailsWilliam E Thomas
final ok
Permanent Service6/8/20066/8/20066/8/2006PPASS
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen
p/s u/g n ok
Permanent Service6/7/20066/7/20066/7/2006PFAIL
DetailsJack Frank
TYLER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
corr. called left message 200.6 shall not ID #6 or smaller neutral,, 110.3(B) shall use manufactures bond screw at p/s, listed equip grd bus at subpanel and terminate equip grds too it,manufactures breakers in subpanel, 110.12(A) seal KOs, 250.8 no SMS for grds or bonds 110.1(A) use sta-con stranded wire 5th terminal at meter
Final6/6/20066/7/20066/7/2006ACANC
DetailsJack Frank
FINAL AND PERMANENT SERVICE TYLER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contrctor requested wrong type of request
Electrical Rough-In6/1/20066/1/20066/1/2006PPART
DetailsJack Frank
TYLER CALL PRIOR TO COMMING OUT CAN WE MAKE THIS YOUR LAST STOP TODAY; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
u/g ok this is behind 8109 w franklin east end