Permit NumberELE06-02092
StatusFinaled
Name GARY'S ELECTRIC
Site Address 2700 W WYMER ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/25/20082/25/20082/25/2008PPASS
DetailsBob Reichert
ok to final
Permanent Service1/31/20071/31/20071/31/2007PPASS
DetailsBob Reichert
gary ; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr made, p/s o/h rec ok
Permanent Service1/30/20071/30/20071/30/2007AFAIL
DetailsBob Reichert
Gary - ###-#### ok per Bob to put in for this am as he had an inspection there already///dld called, left corr notice, nec 408.4 circuit directory shall be complete, concise, clear, 348.30 fmc shall be strapped within 12" of box, 358.30 emt shall be strapped within 3' of box, 314.15 fittings in wet locations shall be listed for use in wet locations,314.28(C) covers shall be provided with suitable screws,BCC all make-up shall be done, range and dryer shall be 4-wire circuits
Final9/1/20069/5/20069/5/2006ACANC
DetailsJack Frank
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
contractor called nr, inspection was called in by owner