Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE06-02364
StatusFinaled
Name PRO-TEC SYSTEMS
Site Address 7316 W FAIRVIEW AVE
Project NameGold's Gym
Customer Number 
ePlanReview 
Description
new electrical for existing building per initial cert of value $521,364.00 ///final value is $559,809 per faxed document 3-7-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/10/20071/11/20071/11/2007APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/10/2007 at 3:09:52 PM. Contact: ###-####. approval on listing ok, ok to final, signed occ card
Final1/8/20071/9/20071/9/2007ANR
DetailsBob Reichert
wayne - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith labels still not correct for luminaires
Final1/2/20071/2/20071/2/2007PPART
DetailsJack Frank
listing for pool heaters ok, still needs to resolve listing of tanning beds
Final12/27/200612/27/200612/27/2006PPART
DetailsJack Frank
wayne ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
T/O ok only corr. posted for pool heaters 3 of them, and all Ambition 250 super power tanning beds shall be locked out and shall not be used till listing problems are corrected, BCC 4.05.(33A) nec 110.2 listed ,labeled, and approved
Final12/26/200612/27/200612/27/2006ANR
DetailsJack Frank
Scheduled by a contractor via Hello! on 12/26/2006 at 6:23:07 PM. Contact: ###-####. need listing information for pool heaters, 3 of them and small tanning beds etl listing is for sun/heat lamps only
Final12/26/200612/26/200612/26/2006PCANC
DetailsPat Lass
Wayne; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett
not ready
Final12/22/200612/26/200612/26/2006ANR
DetailsPat Lass
Scheduled by a contractor via Hello! on 12/22/2006 at 4:44:15 PM. Contact: ###-####.
Final12/22/200612/22/200612/22/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/22/2006 at 7:59:13 AM. Contact: ###-####. no card signed, made list with contr of misc corrections, look for labels on some tanning booths, finish gfci in bath, add sw plates, strap mc, emt, water pipe over elect equip, provide common trip bkr for furniture, will call back next week, contr has list to walk thru
Electrical Rough-In12/14/200612/14/200612/14/2006PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 12/14/2006 at 7:49:57 AM. Contact: ###-####. ok cover ceiling only
Conference12/12/200612/12/200612/12/2006PDONE
DetailsBob Reichert
Scheduled by a contractor via Hello! on 12/12/2006 at 7:21:44 AM. Contact: ###-####. talked about buck-boost xfmrs, application ok, physical install up to contractor
Conference12/8/200612/11/200612/11/2006ADONE
DetailsBob Reichert
WAYNE nOTE: EARLY EARLY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, talked about application of buck- boost transformers, and pool lights. Lights ok, don't need gfci.
Electrical Rough-In11/17/200611/17/200611/17/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/17/2006 at 10:03:24 AM. Contact: ###-####. recpt area walls ok to cover
Permanent Service11/14/200611/15/200611/16/2006APASS
DetailsBob Reichert
or ###-#### blake or wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover sauna walls except for controller, told elect to ground and bond separately derived system,nec 250.30, p/s u/g n ok
Permanent Service11/13/200611/13/200611/13/2006PCANC
DetailsBob Reichert
###-#### - wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
Electrical Rough-In11/9/200611/9/200611/9/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 11/9/2006 at 11:17:56 AM. Contact: ###-####. front soffits and inside sign ckt ok to cover
Electrical Rough-In10/27/200610/27/200610/27/2006PPART
DetailsPat Lass
wayne; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
partial Wall R/I Gym and office restroom area in frontboth floors.
Electrical Rough-In10/18/200610/19/200610/19/2006APASS
DetailsJim Schmer
Scheduled by a contractor via Hello! on 10/18/2006 at 3:42:20 PM. Contact: ###-####. pool walls only
Electrical Rough-In10/6/200610/9/200610/9/2006APART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 10/6/2006 at 4:08:14 PM. Contact: ###-####. ok cover walls only tanning & equip. rms sw corner of building
Electrical Rough-In10/4/200610/5/200610/5/2006APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 10/4/2006 at 2:50:05 PM. Contact: ###-####. front outside u/g and lights
Electrical Rough-In9/28/20069/29/20069/29/2006APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 9/28/2006 at 5:14:26 PM. Contact: ###-####. west end exercise and spinning rms, common wall, east end exercise and corridor walls ok
Electrical Rough-In9/25/20069/25/20069/25/2006PPART
DetailsJack Frank
blake or ###-#### wayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie N E restrms walls hard ceilings, SE front wall
Electrical Rough-In9/15/20069/15/20069/15/2006PPART
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 9/15/2006 at 8:28:21 AM. Contact: ###-####.
mens restroom ok
Electrical Rough-In8/18/20068/18/20068/18/2006PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 8/18/2006 at 9:42:07 AM. Contact: ###-####. E grid pool and spa ok
Electrical Rough-In7/31/20068/1/20068/1/2006APART
DetailsJack Frank
BLAKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs
u/g conduit in front and pool spa lights
Electrical Rough-In7/26/20067/26/20067/26/2006PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/26/2006 at 8:29:39 AM. Contact: ###-####. u/g panel rm ok
Electrical Rough-In7/20/20067/20/20067/20/2006PPART
DetailsPat Lass
###-####. Scheduled by a contractor via Hello! on 7/20/2006 at 11:16:14 AM. Contact: ###-####.
south west parking lot u/G ok
Electrical Rough-In7/14/20067/14/20067/14/2006PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/14/2006 at 11:22:42 AM. Contact: ###-####. ok to cover se part running ns and ew from temp office and center of lot about 30' by center light
Electrical Rough-In7/13/20067/13/20067/13/2006PPART
DetailsPat Lass
Scheduled by a contractor via Hello! on 7/13/2006 at 11:09:47 AM. Contact: ###-####.
Underground on south side 2/3rds up from the building's east end
Electrical Rough-In7/12/20067/12/20067/12/2006PPART
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 7/12/2006 at 9:01:20 AM. Contact: ###-####. ok cover under ground conduit northeast side of parking lot
Electrical Rough-In7/5/20067/6/20067/6/2006APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/5/2006 at 3:46:44 PM. Contact: ###-####. pool & spa bond only no equip. grid
Electrical Rough-In6/30/20066/30/20066/30/2006PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 6/30/2006 at 11:19:17 AM. Contact: ###-####. u/g service and phone conduits
Electrical Rough-In6/29/20066/29/20066/29/2006PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 6/29/2006 at 10:59:19 AM. Contact: ###-####. S W building u/g ok