Permit Information
Permit NumberELE06-02633
StatusFinaled
Name WINTERS ELECTRIC LLC
Site Address 1867 N WILDWOOD AVE
Project Name 
Customer Number06308
ePlanReview 
Description
Electrical Permit - New: Lighting and outlets for TI
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/3/20071/3/20071/3/2007PPASS
DetailsJack Frank
jeff - late as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed
Final12/29/20061/2/20071/2/2007AFAIL
DetailsJack Frank
Address is now on the building - the key for access can be picked up at Ted Mason Office at 1883 N. Wildwood or call Jeff at the above phone number and he will meet you there and open the building.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr. called 400.8 cords shall not pass through ceiling, 410.30 (C) cords for fixtures shall be use listed canopy or use recept and cord cap, 314.27(D) use fan box or support fan to structure, how are hung?
Final12/22/200612/26/200612/26/2006ANH
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, told contr to put in notes how to have access
ELE-Aging Inspection11/8/200611/8/200611/8/2006 PART
DetailsJack Frank
wsuc
Permanent Service9/8/20069/8/20069/8/2006APASS
DetailsBob Reichert
p/s u/g n ok
Electrical Rough-In8/23/20068/24/20068/24/2006APASS
DetailsBob Reichert
Partial rough-in steel stud walls only Contact Ric; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover walls only plus bath lid
Electrical Rough-In8/16/20068/17/20068/17/2006AFAIL
DetailsBob Reichert
Wall Rough-in; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, left corr notice, nec 334.30 fmc shall be secured within 12" of box, 333.30 mc shall be strapped within 12" of box, 358.30(A) emt shall be secured within 3' of box, BCC address shall be posted, approved set of plans shall be on job, job id sticker shall be posted
Electrical Rough-In7/31/20067/31/20067/31/2006PPASS
DetailsMike Kinnear
Rough-in for under slab - document from owner and architect in contractors possession.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok cover under slab conduit.
Conference7/25/20067/26/20067/26/2006PDONE
DetailsBob Reichert
General contractor would like to conference about the classification. Please call with a meeting time.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters met contr and elect to discuss a letter stating purpose of garage
Electrical Rough-In7/17/20067/19/20067/19/2006ANR
DetailsBob Reichert
underground rough-in ; Phone #: ###-#### Internet Inspection Request from: Celinda Winters left correction notice to builder, nec art 511 shall apply, therefore an area classification drawing shall be provided