Permit Information
Permit NumberELE06-02896
StatusFinaled
Name FOUR STAR ELECTRIC INC
Site Address 2515 S FIVE MILE RD
Project NameFire Station #14
Customer Number 
ePlanReview 
Description
install new service, outlets, electrical wiring switches, generator, conduit- all electrical for new construction per initial cert of value $255,000
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/10/20074/11/20074/11/2007APASS
DetailsWilliam E Thomas
Phone #: ###-####
final ok
Final4/3/20074/5/20074/5/2007APART
DetailsBob Reichert
jerri; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walked with elect left list such as labels, warning signs,ground gen set, FACP does not have proper clearance, pole lights need ground lugs, lights, recpts ok, they are working on owner's punch list
Electrical Rough-In3/22/20073/23/20073/23/2007APASS
DetailsBob Reichert
reinspection ceiling Phone #: ###-#### corrections made, ok to cover grid ceilings
Electrical Rough-In3/21/20073/22/20073/22/2007AFAIL
DetailsBob Reichert
Cover on ceiling Phone #: ###-#### called, left correction notice,nec 330.30(B) mc cable shall be strapped within 12" of box, 358.30(A) emt shall be strapped within 3' of box, 110.12(A) unused openings in boxes shall be closed, 410.14(A) fixtures shall not be cord connected unless permitted by 410.30(B) or(C), 348.30 fmc shall be securely fastened by approved means, BCC no ceiling cover shall be done prior to inspection, no lv cables shall be on grid or raceways
Electrical Rough-In2/6/20072/8/20072/8/2007APASS
DetailsBob Reichert
electrial cover upstairs Phone #: ###-#### high bay area ok to cover clgs, (apparatus area)
Electrical Rough-In1/24/20071/25/20071/25/2007APART
DetailsJack Frank
james; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
1st floor walls hard ceilings map rm, fire pole corridor, exercise rm and restrms
Permanent Service12/29/200612/29/200612/29/2006PPASS
DetailsBob Reichert
service inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers p/s u/g n ok
Electrical Rough-In12/19/200612/22/200612/22/2006PPASS
DetailsMike Kinnear
Upstairs cover inspection & service inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok cover ri 2nd floor only
Electrical Rough-In10/3/200610/3/200610/3/2006PPART
DetailsJack Frank
Ufer ground inspection ; Phone #: ###-#### Internet Inspection Request from: Jari Rivers electrode ok
Electrical Rough-In8/29/20068/30/20068/30/2006PPASS
DetailsWilliam E Thomas
Inground inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers
underground ok to generator
Electrical Rough-In8/29/20068/29/20068/29/2006PPART
DetailsJack Frank
ground PVC cover inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers part. u/g ok for u/g from xformer to building
Electrical Rough-In8/28/20068/29/20068/29/2006APART
DetailsJack Frank
cover for pvc ground & UFER Ground inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers electrode only u/g not ready