Permit Information
Permit NumberELE06-03166
StatusExpired
Name GARY'S ELECTRIC
Site Address 1221 S ALBRIGHT ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Rough-In Permanent Service8/25/20068/25/20068/25/2006PFAIL
DetailsBob Reichert
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left corr notice, nec 408.4 circuit directory shall be complete, concise , and explanatory for each circuit, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 406.5,110.12(C) recpt faceplate shall cover opening at recpt and no broken parts shall be used, 334.30 nm cable shall be supported within 12" of flex under bench, 110.26 access and working space shall be provided at panel, BCC no violations shall be retained(open splices over bench),strap flex into panel Note: ok to cover u/g, looked at feeder from in house, it is ok
Rough-In Permanent Service8/24/20068/25/20068/25/2006ACANC
DetailsJack Frank
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs canceled by contr.