Permit Information
Permit NumberELE06-03185
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 10 N ROOSEVELT ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: new building ///Final value is no change//1/4/07 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/12/200612/12/200612/12/2006PPASS
DetailsBob Reichert
JOB COMPLETE FINAL INSPECTION KEY IS ABOVE METER. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr to add conduit straps, ok to final
Permanent Service11/22/200611/22/200611/22/2006PPASS
DetailsBob Reichert
we are ready for a reinspection for perm. service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, p/s u/g n ok
Permanent Service11/21/200611/22/200611/22/2006AFAIL
DetailsJack Frank
WE ARE READY FOR PERM. SERVICE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. called 250.24(C) shall install neutral conductor from meter to p/s not grd wire, 250.30(A)(7) shall install GEC from xformer to u/g copper water not p/s panel bus, 210.5 (A B C ) ID 480/277 120/208 at all locations as code noted states, shall not use tie wraps for flex
Permanent Service11/15/200611/16/200611/16/2006AFAIL
DetailsBob Reichert
PERMANENT SERVICE; Phone #: ###-#### x1 Internet Inspection Request from: BRIAN KEITH called contr to reverse ground and neutral in service panel
Rough-In Permanent Service10/18/200610/19/200610/19/2006ACANC
DetailsJim Schmer
please inspect teh service so that idaho power can energize.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH chng to conference - needs fault current for service jms
Electrical Rough-In9/29/20069/29/20069/29/2006PPART
DetailsJack Frank
need rough in on new building. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. posted for damaged wiring done by concrete contr, shall repair or turn off power, called contr . will address problem, r/i for ceilings ok
Electrical Rough-In8/25/20068/28/20068/28/2006APART
DetailsJack Frank
need inspection on U/G for cover. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH u/g inside of building and electrode ok only outside u/g shall be be 18" or under concrete called
Electrical Rough-In8/25/20068/25/20068/25/2006PCANC
DetailsBob Reichert
need U/G inspection for cover. conduit will be installed by 1:30pm. if possible, please inspect after, thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH talked to elect, he asked to cancel said wanted shop to call for later inspection