Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-03604
StatusFinaled
Name PEAK ELECTRIC
Site Address 9162 W EMERALD ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: New drive-thru coffee house, power, lighting etc.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/20/200612/21/200612/21/2006APASS
DetailsPat Lass
Phone #: ###-#### Internet Inspection Request from: todd hall
Final12/19/200612/19/200612/19/2006PNR
DetailsJack Frank
GC will have building open; Phone #: ###-#### Internet Inspection Request from: todd hall needs gfci for all kit recepts, bond hot and cold water
Final12/18/200612/19/200612/19/2006ANH
DetailsJack Frank
Final inspect. Some exterior wall lights will not be installed till later date.; Phone #: ###-#### Internet Inspection Request from: todd hall no access called
Permanent Service11/28/200611/28/200611/28/2006PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: todd hall corrections made, p/s u/g n ok
Permanent Service11/27/200611/27/200611/27/2006PFAIL
DetailsJack Frank
re-inspect for perm service. Please call Todd with result.; Phone #: ###-#### Internet Inspection Request from: todd hall
corr. not made called
Permanent Service11/22/200611/24/200611/24/2006AFAIL
DetailsJack Frank
Inspection for Perm Service. Please call Todd Hall with any questions ###-####; Phone #: ###-#### Internet Inspection Request from: todd hall fee due corr. called left message see added fee due inspection for notes
Electrical Rough-In11/8/200611/9/200611/9/2006APASS
DetailsJack Frank
re-inspect for building roughin. Please see AJ on site for inspection; Phone #: ###-#### Internet Inspection Request from: todd hall walls and ceiling ok
Electrical Rough-In11/7/200611/8/200611/8/2006AFAIL
DetailsJack Frank
re-roughin for building; Phone #: ###-#### Internet Inspection Request from: todd hall corr. called still needs to strap MC within 12", still needs needs nail plates and 11/4" for MC parallel to studs, inside outside edges for nail plates
Electrical Rough-In11/3/200611/6/200611/6/2006AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: todd called, left message, left corr notice, nec 358.26 there shall not be over 360 degree bends in emt, 358.30(A) emt shall be securely fastened within 3' of box or termination point, 330.30(B) mc shall be securely supported within 12" of box, 300.4(A)&(D) edge of bored holes and mc cable shall be 1 1/4" from edge of framing members 250.86 all metal boxes shall be grounded
Electrical Rough-In11/2/200611/3/200611/3/2006AFAIL
DetailsJack Frank
aj ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see added fee due
Electrical Rough-In11/2/200611/2/200611/2/2006PCANC
DetailsJack Frank
rough in inspect on Human Bean coffee drive thru; Phone #: ###-#### Internet Inspection Request from: todd hall Inspection cancelled from web by: Marsha Smylie
Electrical Rough-In10/9/200610/10/200610/10/2006APASS
DetailsBob Reichert
please inspect uffer ground Call AJ with questions or problems; Phone #: ###-#### Internet Inspection Request from: todd hall ok to pour gec
Electrical Rough-In10/6/200610/9/200610/9/2006ANR
DetailsJack Frank
please do ufer ground inspection; Phone #: ###-#### Internet Inspection Request from: todd hall fee due met contr.
Electrical Rough-In10/6/200610/6/200610/6/2006PPASS
DetailsBob Reichert
UNDERGROUND INSPECTION FOR POLE LIGHT; Phone #: ###-#### Internet Inspection Request from: todd hall ok to cover u/g conduit only, gec not done yet
Electrical Rough-In10/3/200610/4/200610/4/2006AFAIL
DetailsJack Frank
please do trench inspection; Phone #: ###-#### Internet Inspection Request from: todd hall called u/g covered before inspection