Final | 4/11/2007 | 4/12/2007 | 4/12/2007 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### ok
|
Rough-In Permanent Service | 10/18/2006 | 10/18/2006 | 10/18/2006 | P | PASS |
Jack Frank
|
|
|
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman r/i for new part ok, note Jtub not there check for listing when installed p/s o/h rec. ok
|
Rough-In Permanent Service | 10/17/2006 | 10/17/2006 | 10/17/2006 | P | FAIL |
Jack Frank
|
|
|
reinspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman corr. fee due called, 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel, 334.30 staple cables 12" or 8" as code states, 314.43 no screws in plastic boxes, note grd or bond new p/s to water system old part of house, 250.52(A)(1) or 104(A)(1)
|
Electrical Rough-In | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: DJ Carman called, left corr notice, nec 404.8 center operating handle shall not be over 6'-7", 312.5 all conductors entering enclosures shall have abrasion protection, 334.30 nm cable shall be secured within 12" of box and every 4 1/2', 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,210.52(A)(2) 2' wall in kitchen shall have recpt, BCC all make-up shall be done, box water heater, fans, outside nm cable
|