Permit NumberELE06-03829
StatusFinaled
Name COMMERCIAL ELECTRIC
Site Address 1301 N ORCHARD ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Demolition, relocate light fixtures and install new light fixtures. ///final value is $35,858 per faxed document 3-7-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/25/20071/26/20071/26/2007APASS
DetailsBob Reichert
Requesting a final inspection. Phone #: ###-#### corr made, ok to final
Final1/24/20071/25/20071/25/2007AFAIL
DetailsBob Reichert
Requesting a final inspection. Phone #: ###-#### called, left corr notice, nec 605.7 multiwire branch ckts to partitions shall simultaneously disconnect at panelboard where ckt originates, 330.30(B) mc cable shall be strapped within 12" of panel, 408.4 circuit directory shall be permanent, clear, and concise, 110.3(A) equipment shall be listed and labelled, BCC no violations shall be retained, BCC 4-05-33(A)(B) all equipment shall be listed and labelled by a nationally recognized testing laboratory
Final1/12/20071/16/20071/16/2007ANR
DetailsBob Reichert
Requesting a Final inspection.
Please use the West entrance. Phone #: ###-#### not done, see ri for ceilings
Electrical Rough-In1/12/20071/16/20071/16/2007APART
DetailsBob Reichert
Requesting inspection to cover ceilings.
Please use the West entrance. Phone #: ###-#### 1st floor north of hall and east 1/2 only ok to cover clg, fire alarm and lv not terminated , called contr, need panel scheds, no wiring to be left on grid, find out what balance of work is and who doing, no upstairs inspections done yet, no inspections in existing parts of bldg done yet
Final1/9/20071/11/20071/11/2007AFAIL
DetailsJack Frank
Requesting a Final inspection. Phone #: ###-#### no access
Electrical Rough-In1/9/20071/11/20071/11/2007AFAIL
DetailsJack Frank
Requesting inspection to cover ceilings. Phone #: ###-#### no access
Conference12/21/200612/22/200612/22/2006ADONE
DetailsBob Reichert
Requesting a consultation at the job site. ; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty reviewed intent of correction notice written and what not in scope of contr work
Electrical Rough-In12/11/200612/12/200612/12/2006AFAIL
DetailsBob Reichert
Requesting inspection to cover ceiling for area North of main corridor.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty called, left corr notice, BCC no violations shall be retained, NEC 725.3 abandoned Cl 2,3 PLTC cables shall be removed, 300.4(C) cables or raceway type wiring methods shall be supported according to their applicable articles
Electrical Rough-In10/13/200610/16/200610/16/2006PPASS
DetailsBob Reichert
Requesting an inspection to cover.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty walls only ok to cover