Permit NumberELE06-03930
StatusExpired
Name MULLANEY THOMAS F III
Site Address 2105 N 14TH ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In5/3/20075/3/20075/3/2007PPASS
DetailsWilliam E Thomas
dave ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
ri ok
Electrical Rough-In4/27/20074/27/20074/27/2007PCANC
DetailsWilliam E Thomas
thomas ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
1. 210.52B1- breakfast area shall have 20amp cuircuit for all outlets.
2. 210.52C1- countertop receps 2'-4' rule
3. 210.52A2- wall space in kitchen shall have recepticle
4. 300.4A1- nail plates shall be used
5. 310.14- 6" free length of conductor
Electrical Rough-In4/26/20074/26/20074/26/2007PFAIL
DetailsWilliam E Thomas
thomas ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
there is still 15amp wire on 20amp circuits.
Electrical Rough-In4/20/20074/23/20074/23/2007AFAIL
DetailsWilliam E Thomas
thomas; Phone #: ###-#### Internet Inspection Request from: Victoria Beall per thomas mullaney he talked w/ both pat and bill and he stated that they had told him to assign this inspection to bill thomas, that pat couldn't inspect it as bill had inspected it originally.
this indeed up being a confrence, literaly talke about everything
Electrical Rough-In4/20/20074/20/20074/20/2007PNR
DetailsPat Lass
Thomas; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
I talked with Thomas and looked at the job.
I also called Bill. I told Bill and Thomas that It is best if Bill handel this because the work was incomplete when bill wrote the correction and I am umfamilier with that phase of the job and we need to have a face to face meeting because the use of different sizes of wire on circuits and the way circuits are run are hard to trace out.
Thomas will reschedual for mon.
Electrical Rough-In4/16/20074/16/20074/16/2007PFAIL
DetailsWilliam E Thomas
Thomas ; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
to many, consult notice that is posted
Conference3/5/20073/5/20073/5/2007PDONE
DetailsWilliam E Thomas
thomas; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
they had no specific questions were requisting a confrence because the sheet said it was manditory.
Conference2/1/20072/1/20072/1/2007PCANC
DetailsPat Lass
thomas; Phone #: ###-#### Internet Inspection Request from: Darla Downs
thomas is unavailable.