Final | 7/17/2007 | 7/18/2007 | 7/18/2007 | P | FAIL |
Bob Reichert
|
|
|
1:00 please...Duane ###-#### met owner, left correction notice, told owner he has to have contractor permit and final installation, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 314.17(C) nm cable shall be strapped within 8" of box, 312.5 all conductors entering enclosure shall have abrasion protection, 250.53(B)&(G) electrodes shall be minimum 6' apart and driven in flush with or below grade, 406.8(B) outside recpts shall have enclosure that is weatherproof whether or not plug is inserted, 300.14 shall provide minimum 6" free length conductor at each box, 110.3(B) listed equipment shall be installed per instruction included with with listing (tighten clamps), BCC must update permit for service request
|
Electrical Rough-In | 4/2/2007 | 4/3/2007 | 4/3/2007 | A | CANC |
Bob Reichert
|
|
|
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, told owner permit cancelled, he was not happy, said would do as he pleased, and hung up
|
Conference | 3/20/2007 | 3/21/2007 | 3/21/2007 | A | DONE |
Bob Reichert
|
|
|
Dwayne; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called owner, told him permit void, has to get elect contractor to do work and pull permit for any inspections, he will do. He is property owner, but does not live there, and rents out property.
|
Conference | 3/19/2007 | 3/19/2007 | 3/19/2007 | P | NH |
Bob Reichert
|
|
|
dwayne - pls call first; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called 2x, left messages, went to site, left no access card, called 324, told him that people are renting the property and the owner built garage, 324 called and said to pull permit since this not owners principle residence
|
Final | 3/14/2007 | 3/14/2007 | 3/14/2007 | P | FAIL |
Bob Reichert
|
|
|
duane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith told people would leave corr notice, nec300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.17(C) nm cable shall be stapled within 8" of box, 230.24(A) service conductors shall be 8' above roof surface, 250.64(C) gec shall not be spliced, 250.52(A)(3) shall use concrete encased electrode, 312.5 all conductors entering enclosures shall have abrasion protection,240.4 conductors shall be protected against overcurrent according to their ampacity specified in 310.15, BCC all make-up shall be done and inspected prior to device installation
|