Final | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | PASS |
Bob Reichert
|
|
|
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer t/s ok to final, see t/s
|
Temporary Service | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | PASS |
Bob Reichert
|
|
|
questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer corr made, t/s o/h n ok
|
Final | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | FAIL |
Bob Reichert
|
|
|
temp power insp. questions pls call Mike w/Doherty @ ###-####. Scheduled by Heather w/Doherty; Phone #: ###-#### Internet Inspection Request from: Heather Packer called, left corr notice, nec 230.74 service disc shall disconnect all ungrounded conductors simultaneously,312.5 shall provide abrasion protection for all conductors entering enclosure, 250.53(G) electrode shall be flush with or below ground, 408.4 circuit directory shall be correct, BCC job id sticker shall be posted
|