Permit Information
Permit NumberELE06-04690
StatusFinaled
Name MAINLINE ELECTRICAL
Site Address 1845 N WILDWOOD AVE
Project NameSTEELWOOD FLEX CONDOS
Customer Number 
ePlanReview 
Description
12/22/06/ harry's car wash/service outlets, switches upgrade subpanel/initial cert of value $5000/mls ///final value is $5452 per faxed document 4-18-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/26/20073/26/20073/26/2007PPASS
DetailsJack Frank
cindy - on site in another building; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok no card
Final3/23/20073/26/20073/26/2007ANH
DetailsJack Frank
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
notice posted called no response
Final3/23/20073/23/20073/23/2007PFAIL
DetailsJack Frank
Robert; Phone #: ###-#### Internet Inspection Request from: Stacie Backus
corr. fee due 300.10&12 maintain elect,& mech continuity for mc at high bay fixtures, ID white wire mc in subpanel 20 amp 2pole breaker
Final3/21/20073/21/20073/21/2007PFAIL
DetailsJack Frank
robert - ceiling and final; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. called 410.30(C)(1) fixture shall be located directly below the outlet, 600.5(A) shall install required sign branch circuit see added r/i
Electrical Rough-In3/21/20073/21/20073/21/2007PCANC
DetailsJack Frank
robert - ceiling and final; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ceiling ok
Permanent Service2/20/20072/20/20072/20/2007PPASS
DetailsJack Frank
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
p/s u/g new ok
Electrical Rough-In1/4/20071/5/20071/5/2007APASS
DetailsWilliam E Thomas
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smit
1. walls only-ri ok
Electrical Rough-In1/3/20071/3/20071/3/2007PFAIL
DetailsJack Frank
robert Note: walls and perman panel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr fee due called 300.4 nail plates , 250.24(A)(5) isolate grds and neutrals at subpanel 408.41 only 1 neutral wire per terminal
Electrical Rough-In12/22/200612/26/200612/26/2006AFAIL
DetailsBob Reichert
robert-- ###-#### called left corr notice nec 200.6(A) grounded conductor 6 awg or smaller shall be identified by white or gray or 3 continuous white stripes along entire length, 250.119(A) insulated ground shall be green or have green with yellow stripes for id, 300.4(A)&(D) edge of holes and cable shall be 1 1/4" from edge of framing member