Permit Information
Permit NumberELE07-00331
StatusFinaled
Name RUMMER ELECTRIC
Site Address 2022 N FRY ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/24/20074/24/20074/24/2007PPASS
DetailsBob Reichert
Neil ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
Rough-In Permanent Service2/8/20072/9/20072/9/2007APASS
DetailsPat Lass
neil; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
corrections required by bob and jack have been made.
R/I Ok
P/S O/H R Ok
Permanent Service2/6/20072/6/20072/6/2007PFAIL
DetailsJack Frank
neil; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made still needs 11/4" all locations, 250.52(A)(1) GRC to u/g pipe within 5ft, outlet spacing fixed panel of slider din rm called
Electrical Rough-In1/30/20071/30/20071/30/2007PFAIL
DetailsBob Reichert
NEIL; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left corr notice, nec 338.10 & 334 se cable shall be secured within 12" of box, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 210.52(E) shall provide front outdoor recpt, 210.53(D)(2) water pipe ground shall be supplemented by additional electrode per 250.52(A)(2) thru (A)(7), BCC all make-up shall be done-switch ring in north bedroom