DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/19/20074/19/20074/19/2007PPASS
DetailsBob Reichert
Glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus corr made, ok to final
Final4/18/20074/18/20074/18/2007PFAIL
DetailsBob Reichert
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination,110.22 each disconnect shall be legibly marked to show it's purpose, 410.8(A) edge of fixture shall be min 12" from edge of shelf
Rough-In Permanent Service3/9/20073/9/20073/9/2007PPASS
DetailsBob Reichert
glen; Phone #: ###-#### Internet Inspection Request from: Stacie Backus u/g to garage ok, ok to backfill gec, ric ok, p/s u/g n ok
Permanent Service3/6/20073/6/20073/6/2007PCANC
DetailsJack Frank
glenn - ground reinspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith see added r/i
Electrical Rough-In3/6/20073/6/20073/6/2007PPART
DetailsJack Frank
glenn - ground reinspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith electrode ok for concrete cover only