Final | 4/13/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
Jack Frank
|
|
|
Ready for reinspect. Contact is Brian Phone #: ###-#### x0000 ok corr. made
|
Temporary Service | 4/13/2007 | 4/13/2007 | 4/13/2007 | P | PASS |
Jack Frank
|
|
|
Ready for reinspect. Contact is Brian Phone #: ###-#### x0000 t/s u/g new ok
|
Temporary Service | 4/10/2007 | 4/11/2007 | 4/11/2007 | A | FAIL |
Jack Frank
|
|
|
Temp pole is near the xfmer at the south end of the building 100'' east of Sage Construction job trailer. Phone #: ###-#### x0000 corr. called 110.3(B) install manufactures tie bar between neutral buses, use manufactures breakers only, 110.14(A) tighten all screws at bond bushing, 110.12(C) clean all dirt from T/S, 250.64(B) protect #8 GEC, 312.5 use conn. for GEC
|