Final | 2/1/2008 | 2/4/2008 | 2/4/2008 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 2/1/2008 at 11:01:24 AM. Contact: ###-####.
|
Final | 1/22/2008 | 1/23/2008 | 1/23/2008 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/22/2008 at 3:41:46 PM. signed T/O reidentify white wires used for other than neutrals insure electrical and mechanical continuity to gutters properly size pullbox/gutter and correct for deration correct fuses for p-tac's and a/c units bond pool room vents strap flex by panel "P" ground pole light bases and insure proper overcurrent
|
Final | 1/9/2008 | 1/10/2008 | 1/10/2008 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 1/9/2008 at 9:54:57 AM. Contact: ###-####. first floor ok
|
Final | 1/8/2008 | 1/9/2008 | 1/9/2008 | A | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 1/8/2008 at 12:51:34 PM. canc per 324
|
Final | 1/7/2008 | 1/8/2008 | 1/8/2008 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/7/2008 at 5:06:54 PM. 2nd floor hall, ceilings and rooms ok to final
|
Final | 1/3/2008 | 1/3/2008 | 1/3/2008 | A | PART |
Bob Reichert
|
|
|
ok to final 4th floor rooms only
|
Final | 1/2/2008 | 1/3/2008 | 1/3/2008 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 1/2/2008 at 4:04:04 PM. Contact: ###-####. ok cover ceiling 3rd floor ok final 3rd floor rms
|
Final | 12/31/2007 | 12/31/2007 | 12/31/2007 | A | FAIL |
Jack Frank
|
|
|
helped 370 see his response
|
Final | 12/29/2007 | 12/31/2007 | 12/31/2007 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/29/2007 at 7:30:41 AM. Contact: ###-####. wrong length disposal cords, arc fault circuits not correct per room layout, switch plates not flush, met electrician, all 4th floor comments, he has list
|
Electrical Rough-In | 12/26/2007 | 12/27/2007 | 12/27/2007 | A | CANC |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 12/26/2007 at 1:52:09 PM. wrong permit number
|
Electrical Rough-In | 11/13/2007 | 11/13/2007 | 11/13/2007 | P | PART |
Mike Kinnear
|
|
|
RE-INSPECTION FOR T-GRID IN CORRIDOR ON 4TH FLOOR - TOWNPLACE SUITES HOTEL ok cover t-grid 4th floor only
THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall
|
Electrical Rough-In | 11/12/2007 | 11/13/2007 | 11/13/2007 | A | NR |
Bob Reichert
|
|
|
T-GRID COVER INSPECTION FOR THE CORRIDOR ON THE 4TH FLOOR. TOWNPLACE SUITES HOTEL.
THANK YOU Phone #: ###-#### Internet Inspection Request from: Barry Kendall met electrician, wanted inspection for thursday, not today
|
Electrical Rough-In | 10/24/2007 | 10/26/2007 | 10/26/2007 | P | CANC |
William E Thomas
|
|
|
LOBBY AREA - TOWNPLACE SUITES HOTEL
THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall . 1. as noted on prints ok for cover. .
|
Electrical Rough-In | 10/18/2007 | 10/19/2007 | 10/19/2007 | A | PART |
Mike Kinnear
|
|
|
PLEASE INSPECT 1/2 OF THE LOBBY AREA. TOWNPLACE SUITES HOTEL. THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover walls & hard lid ceilings anop
|
Electrical Rough-In | 10/3/2007 | 10/3/2007 | 10/3/2007 | P | PASS |
Mike Kinnear
|
|
|
UNDERGROUND PARKING LOT INSPECTION - P.M. PLEASE Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover under ground conduit for site lighting
|
Electrical Rough-In | 9/14/2007 | 9/14/2007 | 9/14/2007 | P | PART |
Mike Kinnear
|
|
|
READY FOR RE-INSPECTION. 1ST FLOOR GUEST ROOMS - TOWNPLACE SUITES HOTEL. THANKS. Phone #: ###-#### Internet Inspection Request from: Barry Kendall ok cover guest rms walls, ceilings, & corador walls only anop
|
Electrical Rough-In | 9/12/2007 | 9/12/2007 | 9/12/2007 | P | FAIL |
Bob Reichert
|
|
|
READY FOR RE-INSPECTION @ TOWNPLACE SUITES - 1st FLOOR GUEST ROOMS. THANKS Phone #: ###-#### Internet Inspection Request from: Barry Kendall met elect, left corr notice, nec 110.26(F)(1) there shall be drip protection over panels, 362.30(A) ent shall be secured within 3' of termination and every 3', 330.30(B) mc cable shall be secured within 12" of box and every 6', BCC all make-up shall be done
|
Electrical Rough-In | 9/6/2007 | 9/6/2007 | 9/6/2007 | P | NR |
Bob Reichert
|
|
|
Danny 1st floor guest rooms Phone #: ###-#### rooms not ready, met elect told to have all work done before call for cover, i.e. smurf for low voltage, fire alarm piping, covers on boxes, strapping for panel conduit, drip shields over panels, some rooms appear to need extra receptacles installed
|
Permanent Service | 9/6/2007 | 9/6/2007 | 9/6/2007 | P | PASS |
Bob Reichert
|
|
|
met elect, talked with 412 and he had looked at corrections that 315 wrote and they were ok. Looked at u/g per ri inspection this date, put sticker on switchgear, p/s u/g n ok, there is not a meter socket on transformer
|
Electrical Rough-In | 9/6/2007 | 9/6/2007 | 9/6/2007 | P | PASS |
Bob Reichert
|
|
|
looked at u/g coming out of building going to transformer, said ok to cover . Depth and spacing ok
|
Electrical Rough-In | 9/5/2007 | 9/6/2007 | 9/6/2007 | A | PART |
William E Thomas
|
|
|
wayne - underground conduit at town place suites Phone #: ###-#### . 1. depth by the transformer ok. they will uncover the run at the building for inspection also.
|
Permanent Service | 8/24/2007 | 8/24/2007 | 8/24/2007 | P | FAIL |
Mike Kinnear
|
|
|
wayne Phone #: ###-####Note: for east evelator and main gear there is no inspection for under ground conduit to the service equipment.
|
Permanent Service | 8/22/2007 | 8/23/2007 | 8/23/2007 | A | FAIL |
Jack Frank
|
|
|
wayne Phone #: ###-####Note: main gear east elevator corr grd water within 5ft needs bell ends for u/g pvc, plastic or listed conn for GEC, terminate all GEC to neutral bus
|
Electrical Rough-In | 8/23/2007 | 8/23/2007 | 8/23/2007 | A | PART |
Jack Frank
|
|
|
wayne Phone #: ###-####Note: main gear east elevator walls and hard ceilings elevator rm
|
Electrical Rough-In | 8/3/2007 | 8/6/2007 | 8/6/2007 | A | PART |
Mike Kinnear
|
|
|
wayne - 2nd floor rooms and hallways, wall cover inspection Phone #: ###-#### ok cover walls ceiling & corador walls anop ok cover equipment elevator rm 1st floor west end
|
Electrical Rough-In | 7/23/2007 | 7/24/2007 | 7/24/2007 | A | PART |
Bob Reichert
|
|
|
wayne - cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang marked plans 3rd floor stating stairwells only ok to cover
|
Electrical Rough-In | 6/29/2007 | 7/2/2007 | 7/2/2007 | A | PART |
Mike Kinnear
|
|
|
wayne - 3rd fl wall cover; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok cover walls & ceiling rooms only & corador walls third floor anop
|
Electrical Rough-In | 6/11/2007 | 6/11/2007 | 6/11/2007 | P | PART |
Jack Frank
|
|
|
josh - 4th floor; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok anop
|