Permit Information
Permit NumberELE07-02005
StatusFinaled
Name HIGH WATER ELECTRIC
Site Address 3419 N COLE RD
Project NameCOLE VILLAGE
Customer Number 
ePlanReview 
Description
add elecrical panel for hair cutting station, plugs, and floor outlets per initial cert of value is $12,500//6/4/07 LEG ///final value remains the same per faxed document 8-6-07ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/9/20077/10/20077/10/2007PPASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/9/2007 at 10:04:17 PM. Contact: ###-####. ok card signed
Final7/8/20077/9/20077/9/2007AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/8/2007 at 7:57:03 PM. Contact: ###-####. corr 250.122 shall not use #12 for 30amp W H circuits from panel tp WH and all jboxes called
Permanent Service7/1/20077/2/20077/2/2007APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/1/2007 at 10:15:18 PM. Contact: ###-####. p/s u/g new ok
Permanent Service6/26/20076/27/20076/27/2007PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 6/26/2007 at 7:25:36 PM. Contact: ###-####. corr called all violations not done new one created shall use manufactures listed bonding means not a #10 jumper for 200 amp
Final6/25/20076/26/20076/26/2007PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 6/25/2007 at 9:39:31 PM. Contact: ###-####. no pwer for new p/s can't do a final without power c alled
Permanent Service6/25/20076/26/20076/26/2007PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 6/25/2007 at 9:38:46 PM. Contact: ###-####. called corr 250.92(A)(3) needs bonding both ends of conduit for GEC, shall terminate GEC to old GEC buse or tap to it, install bond strap at new 200 amp P/S needs labels noting both disconnects for tennant
Electrical Rough-In6/12/20076/13/20076/13/2007APASS
DetailsWilliam E Thomas
Scheduled by a contractor via Hello! on 6/12/2007 at 2:00:41 PM. Contact: ###-####.
walls ok to cover cielieng at later date
Electrical Rough-In6/11/20076/12/20076/12/2007PFAIL
DetailsPat Lass
Scheduled by a contractor via Hello! on 6/11/2007 at 7:53:29 PM. Contact: ###-####.
300.11 (b) & (c)
Electrical Rough-In6/8/20076/11/20076/11/2007AFAIL
DetailsBob Reichert
Dave; Phone #: ###-#### Internet Inspection Request from: Hattie James called, left corr notice, nec 358.30(A) emt shall be supported within 12" of box, 330.30(B) mc cable shall be secured within 12" of box, and not over 6' in length without strapping,(whips) 300.4(A)&(D) edge of bored holes and raceways shall be 1 1/4" from edge of framing members, 300.11(A) support wires shall be provided for fixtures, BCC no violations shall be retained- no lv wiring on grid
Electrical Rough-In6/5/20076/6/20076/6/2007APART
DetailsJack Frank
Dave; pouring concrete - partial rough-in; Phone #: ###-#### Internet Inspection Request from: Hattie James u/g ok