Permit Information
Permit NumberELE07-02173
StatusFinaled
Name ATLAS ELECTRIC
Site Address 1815 N CURTIS RD
Project Name 
Customer Number 
ePlanReview 
Description
rewiring on remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/24/20079/24/20079/24/2007PPASS
DetailsBob Reichert
dave - please call for acess Phone #: ###-#### corrections made, ok to final
Final9/20/20079/21/20079/21/2007AFAIL
DetailsJack Frank
DAVE Phone #: ###-#### corr. fee due called 210.52(A) needs outlet liv. rm by fireplace and eating bar wall space, 410.8 clearence for all bed rm closet fixtures, box fill old metal box basement W H drain pump
called left message
Electrical Rough-In7/19/20077/19/20077/19/2007PPASS
DetailsWilliam E Thomas
randy Phone #: ###-####
1. upstairs ok--the first floor
Electrical Rough-In7/17/20077/17/20077/18/2007PFAIL
DetailsBob Reichert
randy Phone #: ###-#### called, left message, left corr notice, nec 210.52 shall provide recpts at front and rear of dwelling, in hall over 10' long, in walls over 2', within 6' of room entry and not over 12' apart along wall line, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.17 shall staple nm cable within 8" or 12" of appropriate boxes, 300.14 shall provide 6" free conductor length at boxes, BCC no violations shall be retained
Permanent Service6/25/20076/25/20076/25/2007PPASS
DetailsBob Reichert
randy Phone #: ###-#### corrections made, p/s o/h rec ok
Permanent Service6/20/20076/20/20076/20/2007PFAIL
DetailsBob Reichert
joe Phone #: ###-#### called , corrections not done plus created new violations, nec 312.5 shall provide abrasion protection for all conductors entering enclosures, 250.64(C) shall use irreversible splice on gec, did not fix panel door or ground water pipe,fee due
Permanent Service6/15/20076/15/20076/15/2007PFAIL
DetailsBob Reichert
randy ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called left corr notice, nec 352.30 & 358.30 conduit shall be supported within 3' of panel, 110.12(C) there shall be no damaged parts-panel cover hinge, grounding electrode conductor, 250.52(A) shall use metal water pipe for gnd electrode,210.53(D)(2) shall supplement electrode with 2 ground rods, 210.53(G) grd rods shall be driven 8' into ground, upper end flush with or below ground, 110.3(B) shall use listed gnd clamps,BCC no violations shall be retained