Permit Information
Permit NumberELE07-02326
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 12534 W CEDARWOOD DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/10/200710/11/200710/11/2007APASS
DetailsJack Frank
eric - re-inspection Phone #: ###-#### ok
Final10/9/200710/10/200710/10/2007AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 10/9/2007 at 12:02:52 PM. Contact: ###-####. corr. 408.4 panel directory be specific, 410,8 clearence for closet fixtures, and install all closet fixtures, called
Rough-In Permanent Service7/5/20077/6/20077/6/2007PPASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 7/5/2007 at 11:39:37 AM. Contact: ###-####. r/i ok corr. made found listing on tub
Rough-In Permanent Service7/2/20077/3/20077/3/2007AFAIL
DetailsJack Frank
zane Phone #: ###-#### see added p/s , r/i failed install for boxes, complete all makeup outsie boxes, 334.23 protect all cables high and low volt by attic accesses, 300.4(A)(1)&(D) nail plates and 11/4" for low voltage, 110.2 Jtub not listed by testing lab called
Permanent Service7/3/20077/3/20077/3/2007APASS
DetailsJack Frank
zane Phone #: ###-#### p/s u/g new ok
Electrical Rough-In6/28/20077/2/20077/2/2007AFAIL
DetailsBob Reichert
jason Phone #: ###-#### called, left message, 219.52(A)(1) recpts shall be installed such that no point along wall is over 6' from outlet, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member