Final | 11/14/2007 | 11/15/2007 | 11/15/2007 | A | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 11/14/2007 at 12:51:35 PM. Contact: ###-####. ok final note signed card
|
Rough-In Permanent Service | 9/13/2007 | 9/13/2007 | 9/13/2007 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 9/13/2007 at 11:11:53 AM. Contact: ###-####. ok cover ri service approved by 370 9/13/07 am
|
Rough-In Permanent Service | 9/12/2007 | 9/13/2007 | 9/13/2007 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. see ri and p/s
|
Electrical Rough-In | 9/13/2007 | 9/13/2007 | 9/13/2007 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. called contr, left corr notice: nec 300.4 edge of bored holes shall be 1 1/4" from edge of framing members, 348.30(A) fmc shall be strapped within 12" of panels, 110.26(F)(1)(b) ducts over dedicated panel space shall have drip protection, 348.42 angle connectors shall not be used for concealed raceway installations, BCC inspection of raceways shall be made before cover
|
Permanent Service | 9/13/2007 | 9/13/2007 | 9/13/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. p/s u/g n ok, 4 meters
|
Electrical Rough-In | 9/13/2007 | 9/13/2007 | 9/13/2007 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/12/2007 at 1:01:31 PM. Contact: ###-####. cloned wrong permit
|
Electrical Rough-In | 8/3/2007 | 8/3/2007 | 8/3/2007 | P | PASS |
Mike Kinnear
|
|
|
zane - 4 outlets underground Phone #: ###-#### ok cover under slab conduit & boxes
|