Permit NumberELE07-03488
StatusExpired
Name WILLIAM EISINGER
Site Address 12877 W GRENADIER DR
Project Name 
Customer Number 
ePlanReview 
Description
wiring for the garage only
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In10/15/200710/16/200710/16/2007APASS
DetailsJack Frank
BILL ###-#### ok
Electrical Rough-In10/15/200710/15/200710/15/2007PFAIL
DetailsJack Frank
bill Phone #: ###-#### corr called all corr. not made still loose crimps, box fill ,6" free length,
Electrical Rough-In10/11/200710/12/200710/12/2007AFAIL
DetailsBob Reichert
bill Phone #: ###-#### called owner, left correction notice, nec 314.20 boxes shall be flush with finished surface- outside garage doors lights, 300.4(D) edge of nm cable shall be 1 1/4" form edge of framing member, 300.14 at least 6" of free conductor shall be provided in boxes, 110.12(C) there shall be no broken boxes(openings shall be closed), 110.14(A) connection of conductors shall ensure a thoroughly good connection (ground crimps) Note: no service or panel, see ele07-03473