Permit Information
Permit NumberELE07-03835
StatusFinaled
Name GEORGES ELECTRIC
Site Address 2811 N SELKIRK DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/7/20087/7/20087/7/2008PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/7/2008 at 7:34:54 AM. Contact: ###-####. ok to final, no esc this project
Electrical Rough-In1/20/20081/22/20081/22/2008APASS
DetailsWilliam E Thomas
key is at door on side of home where garage is. Phone #: ###-#### Internet Inspection Request from: Cevyn Recla
. 1. final ok. .
Electrical Rough-In1/17/20081/17/20081/17/2008AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 1/17/2008 at 6:25:19 AM. Contact: ###-####. called, left correction notice, nec 250.52(A)(1) shall provide connection for incoming water pipe, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 210.52(A)(2) shall provide receptacle in 2' wall in kitchen, 250.148(C) shall ground metal boxes, 314.20 boxes shall be flush with finished surface in walls of combustible material, NOTE: shall locate listing label for jetted tub
Permanent Service11/15/200711/15/200711/15/2007PPASS
DetailsPat Lass
george Phone #: ###-####
ground rods ok check water grounding/bonding on rough-in
P/S U/G R Ok to change from overhead to u/g