Permit Information
Permit NumberELE07-03868
StatusFinaled
Name GIETZEN ELECTRIC INC
Site Address 2810 W ELDER ST
Project NameAPPLEBEES
Customer Number 
ePlanReview 
Description
Electricl see attachements - $120,000 per initial cert of value ///final value remains the same per faxed document 5-5-08ps
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/2/20084/2/20084/2/2008PPASS
DetailsWilliam E Thomas
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen
. .1. final ok. . .
Final4/1/20084/1/20084/1/2008PPART
DetailsBob Reichert
Asking for a final on Kitchen Line only. Phone #: ###-#### Internet Inspection Request from: Paula Gietzen kitchen areas only ok, need to see rest of job
Electrical Rough-In3/17/20083/18/20083/18/2008APASS
DetailsBob Reichert
above ceiling inspection Phone #: ###-#### Internet Inspection Request from: Paula Gietzen ok to cover ceiling
Conference3/10/20083/11/20083/11/2008ACANC
DetailsJack Frank
Underground site work Phone #: ###-#### Internet Inspection Request from: Paula Gietzen
Electrical Rough-In3/11/20083/11/20083/11/2008APART
DetailsJack Frank
Underground site work Phone #: ###-#### Internet Inspection Request from: Paula Gietzen u/g ok
Electrical Rough-In3/7/20083/10/20083/10/2008AFAIL
DetailsBob Reichert
Underground inspection. Trenching and pipe for sign and pole bases Phone #: ###-#### Internet Inspection Request from: Paula Gietzen called contractor, left correction notice and card, BCC shall not cover u/g before inspection, shall provide proper bedding per NEC 300.5, no rocks in u/g. see 1st pole base on right middle of lot for do not cover card
Electrical Rough-In2/19/20082/19/20082/19/2008PPASS
DetailsBob Reichert
Wall - Rough in
Doug Gietzen is on site ###-#### Phone #: ###-#### Internet Inspection Request from: Paula Gietzen walls only ok to cover
Permanent Service2/19/20082/19/20082/19/2008PPASS
DetailsBob Reichert
Wall - Rough in
Doug Gietzen is on site ###-#### Phone #: ###-#### Internet Inspection Request from: Paula Gietzen p/s u/g n ok
Rough-In Permanent Service12/20/200712/21/200712/21/2007APART
DetailsMike Kinnear
Request underground inspection Phone #: ###-#### Internet Inspection Request from: Paula Gietzen ok cover under slab conduit note service not ready
Electrical Rough-In12/19/200712/19/200712/19/2007PPASS
DetailsWilliam E Thomas
. 1. concrete encased electrode ok for cover in footing. .
Electrical Rough-In12/6/200712/7/200712/7/2007AFAIL
DetailsWilliam E Thomas
U-Fer Ground Inspection only. Concrete guys want to pour after 1pm Friday, December 07,2007. Thank you. Phone #: ###-#### Internet Inspection Request from: Paula Gietzen
. 1. Electrode not in proper position, needs to be on the bottom of the footing. .
Temporary Service11/21/200711/21/200711/21/2007PPART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen needs inspection for job shack feeder t/s o/h new ok
Temporary Service11/20/200711/21/200711/21/2007ACANC
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Paula Gietzen t/w contractor temp not ready he will recall back in with ready