Rough-In Permanent Service | 1/14/2008 | 1/14/2008 | 1/14/2008 | P | PASS |
Mike Kinnear
|
|
|
richard Phone #: ###-#### ok ri p/s o/h reconnect ok
|
Final | 1/14/2008 | 1/14/2008 | 1/14/2008 | P | PASS |
Mike Kinnear
|
|
|
richard Phone #: ###-#### ok final
|
Final | 12/31/2007 | 1/4/2008 | 1/4/2008 | A | FAIL |
Jack Frank
|
|
|
richard Phone #: ###-####corr. called T310.15(B)(2)(a) derate wires 2" pvc, 312.5 cables not allowed in 2" pvc,also provide connectors for cables in back of panel, 200.6&7 shall not ID 6 or smaller, red #12 used as neutral, re ID white in 10/2 for water heater, 250.53(D)(2) needs 2 grd rods, 230.24 make sure service drop and drip loop have required clearence note remove old #8 GEC from service panel and call for r/i p/s not final
|