Permanent Service | 12/31/2007 | 12/31/2007 | 12/31/2007 | P | PASS |
Pat Lass
|
|
|
dan - if you have any questions call either dan or jack frank Phone #: ###-#### P/S O/H R Ok
|
DOC - Permit Finaled | 12/31/2007 | 12/31/2007 | 12/31/2007 | P | PASS |
Pat Lass
|
|
|
|
Permanent Service | 12/28/2007 | 12/28/2007 | 12/28/2007 | P | NR |
Jack Frank
|
|
|
dan Phone #: ###-#### needs to change or protect #8 GEC, 250.52(A !), 104(A!) shall grd within 5ft or bond water, T 220.55 shall install required size circuit for range , 314.3 needs bond bushings for metallic raceways in plastic jbox
|