Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE08-00320
StatusFinaled
Name TOMLINSON ELECTRIC
Site Address 5204 N DECATUR DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In3/3/20083/4/20083/4/2008APASS
DetailsJack Frank
jack all issues have been corrected. thanks bob Phone #: ###-#### Internet Inspection Request from: robert tomlinson
ok
Final3/4/20083/4/20083/4/2008APASS
DetailsJack Frank
jack all issues have been corrected. thanks bob Phone #: ###-#### Internet Inspection Request from: robert tomlinson
p/s u/g new ok
Rough-In Permanent Service2/27/20082/28/20082/28/2008AFAIL
DetailsJack Frank
bob - also the kitchen and garage Phone #: ###-#### called corr posted 300.4 nail plates and 11/4", 314.16 box fill, 300.14 6" free length, 250.148 slpice all equip grds together at boxes, 250.52(A)(1) grd water within 5ft of metal u/g water pipe from service not sub panel312.5 (C) exception pvc shall exit top of panel