Permit Information
Permit NumberELE08-00459
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 2854 S FEATHERLY WAY
Project NameSystem Tech INC
Customer Number 
ePlanReview 
Description
complete wiring for 12,000 sq foot core and shell $51,533 per initial cert of value
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/17/20089/18/20089/18/2008APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/17/2008 at 8:08:27 AM. Contact: ###-####. corrections made, ok to final, signed occupancy card, could not add esc comments
Final9/15/20089/15/20089/15/2008PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/15/2008 at 8:18:41 AM. Contact: ###-####. called, left correction notice, NEC 330.30(A)&(B) approved securing devices shall be used and mc shall be secured within 12" of cable termination, 300.11(A) support wires shall provide secure support and be secured at both ends, BCC all work shall be completed, (front counter)
Final9/12/20089/12/20089/12/2008PCANC
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 9/12/2008 at 10:24:32 AM. Contact: ###-####. wrong type inspection
Conference9/12/20089/12/20089/12/2008PDONE
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 9/12/2008 at 10:24:32 AM. Contact: ###-####. drop ceiling support needs to be id., use listed supports, 12inch from boxes, & 6ft when dasey chained, wire needs to be connected from ceiling & grid.
Permanent Service8/20/20088/21/20088/21/2008APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 8/20/2008 at 3:05:10 PM. Contact: ###-####. talked to contr, at time of final accessibility to breaker shall meet NEC 240.24 p/s u/g new ok
Permanent Service8/19/20088/20/20088/20/2008AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 8/19/2008 at 11:47:47 AM. Contact: ###-####. called, left correction notice, NEC 404.8 center of grip of operating handle shall not be over 6'-7" above floor, 110.22 disconnects shall be labelled to indicate its purpose and be of sufficient durability to withstand its environment, 250.68 connection to grounding electrode shall be accessible, 358.30(A) shall strap emt within 3' of box,250.52 shall provide concrete encased electrode, BCC shall provide separate electrical permit for 2nd meter
Electrical Rough-In8/12/20088/12/20088/12/2008PPART
DetailsBob Reichert
Scheduled by a contractor via Hello! on 8/12/2008 at 9:38:44 AM. Contact: ###-####. ok to cover ceilings part lobby, conference, and shower rooms
Electrical Rough-In8/7/20088/7/20088/7/2008PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 8/7/2008 at 8:28:53 AM. Contact: ###-####. hard lids for halls and baths ok to cover
Electrical Rough-In7/29/20087/29/20087/29/2008PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 7/29/2008 at 10:36:53 AM. Contact: ###-####. ok cover under ground conduit for site lighting in front of building
Electrical Rough-In7/28/20087/28/20087/28/2008PPASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/28/2008 at 8:53:55 AM. Contact: ###-####. walls only ok to cover except warehouse area
Electrical Rough-In7/24/20087/25/20087/25/2008PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/24/2008 at 11:43:22 AM. Contact: ###-####. called contractor, left correction notice, NEC 300.4 where subject to physical damage, shall protect cables if not 1 1/4" from face of framing members,BCC Shall complete all work before inspection, shall not use valley of steel studs to secure cable, shall have address posted
Electrical Rough-In4/14/20084/14/20084/14/2008PPART
DetailsBob Reichert
zane Phone #: ###-#### called contractor - north side of property line u/g for area lighting only ok to cover, under parking lot driveway entrance not deep enough, contractor will check and recall
Electrical Rough-In3/21/20083/21/20083/21/2008PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 3/21/2008 at 7:00:54 AM. Contact: ###-####. ok cover under slab conduit only
Electrical Rough-In3/6/20083/7/20083/7/2008APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/6/2008 at 2:51:08 PM. Contact: ###-####. ok to pour under slab only, called contractor to ensure sand bedding for raceways
Conference2/27/20082/28/20082/27/2008ACANC
DetailsBob Reichert
Scheduled by a contractor via Hello! on 2/27/2008 at 1:46:29 PM. Contact: ###-####. Inspection cancelled from web by: Patricia Smith