Final | 4/26/2008 | 4/28/2008 | 4/28/2008 | A | PASS |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: Mick Williams
|
Final | 4/23/2008 | 4/24/2008 | 4/24/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Mick Williams called, left correction notice, BCC shall install outside fixtures, shall meet 2005 NEC requirements, NEC 210.52 shall meet outlet spacing in kitchen, 210.8(A)(6) kitchen receptacles shall be gfci protected, 334.15(B) nm cable shall be protected for microwave, 110.3(B) equipment shall be installed per listing- reverse polarity by patio door, 406.5 shall install receptacle faceplate for disposal,408.4 circuit directory shall be clear, concise and explanatory for each circuit, 422.31(B) shall install disconnect for hot water heater, Note a/c shall be installed or circuiting abandoned
|
Permanent Service | 3/19/2008 | 3/20/2008 | 3/20/2008 | P | PASS |
Bob Reichert
|
|
|
Grounding electrode is in front of house just left of front door. Phone #: ###-#### Internet Inspection Request from: Mick Williams corrections made, left correction notice to owner stating he has 24 hours to acquire permit to bring house up to code or further action will be taken such as removal of power. (Posted on garage door inside garage) p/s o/h n ok
|
Permanent Service | 3/19/2008 | 3/20/2008 | 3/19/2008 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Mick Williams Inspection cancelled from web by: Mick Williams
|
Permanent Service | 3/18/2008 | 3/19/2008 | 3/19/2008 | A | FAIL |
Jack Frank
|
|
|
Ready for service inspection so we can get IPCo connected. Then we will turn on power and determine what needs to be fixed. Phone #: ###-#### Internet Inspection Request from: Mick Williams corr called 312.5(C) exception ser not allowed in conduit, unless it exits the top, needs concrete encased electrode, 250.104(A)(1) bond water to service not sub panel, 110.3(A&B) use proper sized lugs or terminals for conductors250.142(B) 4 wire recepts and pigtails for range and dryer, 100.12(A) seal unused 2" top of sub panel
|