Permit Information
Permit NumberELE08-01064
StatusFinaled
Name RUMMER ELECTRIC
Site Address 3319 N ACRE LN
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/16/20089/17/20089/17/2008APASS
DetailsBob Reichert
Neil Phone #: ###-#### corrections made, ok to final, could not add esc comments
Final9/9/20089/9/20089/9/2008PFAIL
DetailsBob Reichert
Neil Phone #: ###-#### called, left correction notice, NEC 210.11(C)(3) bathroom 20amp branch circuit shall not supply other outlets (a/c), 352.30(A) pvc shall be securely fastened within 3' of termination, 250.32(A) structure supplied by feeder shall have grounding electrode system installed,314.21 shall repair drywall for closet lights, BCC shall install fluorescent tubes, shall install under-counter lights
Electrical Rough-In8/7/20088/7/20088/7/2008PPASS
DetailsBob Reichert
neil - floor heat inspection Phone #: ###-#### ok to cover floor heat, 2 baths
Electrical Rough-In6/23/20086/24/20086/24/2008APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/23/2008 at 10:42:45 PM. Contact: ###-####. corrections made, ric ok
Permanent Service6/24/20086/24/20086/24/2008APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/23/2008 at 10:42:45 PM. Contact: ###-####. corrections made, p/s u/g n ok
Rough-In Permanent Service6/23/20086/23/20086/23/2008PFAIL
DetailsBob Reichert
Neil ###-#### called, left message, left correction notice, BCC all ri shall be done, all make-up shall be done, NEC 210.52(H) hallway over 10' shall have receptacle outlet installed, 210.(A)(1),(2) wall over 2' shall have receptacle installed, 314.25boxes shall have cover installed- up lighting, 300.4(A)(1) nailplate shall be installed if edge of bored hole less than 1/14" from edge of framing member, 334.30 shall secure nm cable within 12" of panel
Electrical Rough-In4/30/20084/30/20084/30/2008PPASS
DetailsBob Reichert
neal Note: underground Phone #: ###-#### corrections made, ok to cover u/g house to garage
Electrical Rough-In4/28/20084/28/20084/28/2008PFAIL
DetailsBob Reichert
neal Note: underground Phone #: ###-#### called, left message, left correction notice, NEC 300.5(D)(4) raceway subject to physical damage shall be schedule 80