Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberELE08-01140
StatusFinaled
Name CAPITOL ELECTRIC
Site Address 7008 W MCMULLEN ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Al electrical wiring for new home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/20/200811/20/200811/20/2008APASS
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Jim Williams ok final correction made note esc permit has been finaled
Final11/18/200811/18/200811/18/2008PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams called left correction notice, NEC 110.22 shall identify and label disconnects (main and heaters), 422(B)(1)(2) disposal cord shall not be over 3' long, 250.104 shall bond water piping systems, 680 and BCC shall see u/g before cover to hot tub, shall provide disconnect and receptacle, shall see listing
Electrical Rough-In6/20/20086/20/20086/20/2008PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams ric ok
Final6/19/20086/20/20086/20/2008PCANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams Inspection cancelled from web by: Jim Williams
Permanent Service5/11/20085/12/20085/12/2008APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s u/g n ok
Permanent Service5/6/20085/7/20085/7/2008ACANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams see conference
Conference5/7/20085/7/20085/7/2008ADONE
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Jim Williams met contractor, talked about sub-panel clearance requirements and piping interferences for basement panel, rest ok, will recall for p/s