Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE08-01255
StatusFinaled
Name PEAK ELECTRIC
Site Address 622 W IDAHO ST
Project NameADELMAN BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Electrical Installation of 1 200 AMP Panel, Lighting and misc. material
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/30/200810/1/200810/1/2008APASS
DetailsJack Frank
ok no card
Final9/30/20089/30/20089/30/2008PCANC
DetailsJack Frank
Final Electrical inspection, James is onsite Journeyman- Corrections made Phone #: ###-#### Internet Inspection Request from: Beka Hereau called will meet contr in AM he said they will have it opened at 7:15 am
Final9/29/20089/30/20089/30/2008AFAIL
DetailsJack Frank
Final Electrical Inspection, please call James @ ###-#### Phone #: ###-#### Internet Inspection Request from: Beka Hereau corr 300.7 seal freezer and cooler raceways(inside), 314.16 box fill handy box kit. equip, also strap MC 330.30, 100.26 (F)(1) clearence for panel, in room with WH upstairs, 250.104(A)(1) bond hot and cold T250.66, 210.8 com. kit gfci for 125 V recepts install all covers
Electrical Rough-In9/23/20089/23/20089/23/2008PPASS
DetailsPat Lass
Cover inspection for Kitchen Cieling Inspection job onsite contact Luke W. ###-#### Phone #: ###-#### Internet Inspection Request from: Beka Hereau
Electrical Rough-In7/3/20087/3/20087/3/2008PPASS
DetailsWilliam E Thomas
Rough _in down stairs cieling cover inspection. Electrician on-site James ###-#### Phone #: ###-#### Internet Inspection Request from: Beka Hereau
. .1. 1st floor drop cieling ok to cover. . .
Electrical Rough-In7/2/20087/3/20087/3/2008AFAIL
DetailsWilliam E Thomas
Downstairs cieling rough-in to cover Phone #: ###-#### Internet Inspection Request from: Beka Hereau
. .1. 300.11A--support wires shall be secured at both ends. . .
Electrical Rough-In6/10/20086/11/20086/11/2008APASS
DetailsWilliam E Thomas
Down Stairs electrical wall inspection. James @###-#### will be on site Phone #: ###-#### Internet Inspection Request from: Beka Hereau
. .1. furred out wall on 1st floor ok for cover. . .
. .2. no cielling at this time. . .
Electrical Rough-In5/22/20085/23/20085/23/2008PPART
DetailsPat Lass
Rough-In inspection upstairs only Phone #: ###-#### Internet Inspection Request from: Beka Hereau
2nd floor walls ok