Permit Information
Permit NumberELE08-01641
StatusFinaled
Name CLARENCE YORK
Site Address 1911 W CATALDO DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/23/200911/24/200911/24/2009APASS
DetailsBob Reichert
Jim Phone #: ###-#### ok to final
Electrical Rough-In11/12/200911/13/200911/13/2009APASS
DetailsBob Reichert
jim Phone #: ###-#### ric ok rest of shop, south and west area
Electrical Rough-In4/2/20094/3/20094/3/2009APASS
DetailsBob Reichert
Jim Phone #: ###-#### corrections made, ric ok
Electrical Rough-In3/31/20093/31/20093/31/2009PFAIL
DetailsJack Frank
Jim Phone #: ###-#### met owner corr posted 250.148(D) grd or replace metal mud rings on plastic boxes, 255.119 shall not ID #6 or smaller eguip grd in feeder conduit from house to shop, 410.62 (C) elect discharge fixtures shall be located dirtly below recept, 110.3(A&B) shall use use boxes listed fro ceiling use, and replace all damages 2,3 gang boxes with broken clamps(314.17(A&C),,,,,300.4(G) needs bushinf fo #4 and larger, 250.4(A)(3&4) tighten bond screw at p/s
Electrical Rough-In3/19/20093/20/20093/20/2009ACANC
DetailsBob Reichert
tim Phone #: ###-#### see conference, wrong type request
Conference3/20/20093/20/20093/20/2009ADONE
DetailsBob Reichert
tim Phone #: ###-#### met owner, talked about make-up, free length of conductor, 12" and 8" securing of cable out of boxes, extension rings for boxes, box support to be secure, outside lights to be in boxes, horizontal support of mc cable on trusses
Rough-In Permanent Service12/1/200812/1/200812/1/2008PCANC
DetailsMike Kinnear
Jim Phone #: ###-#### wrong type inspection
Conference12/1/200812/1/200812/1/2008PDONE
DetailsMike Kinnear
Jim Phone #: ###-#### needs to clean up main service sub connected free air wires. shop sub panel needs to isolate the neut. bond metal building, frame & support service panel properly, use plastic romex connector for ground wire properly mount boxes,& use green screw for metal boxes.
Electrical Rough-In8/28/20088/28/20088/28/2008PPASS
DetailsMike Kinnear
Jim- early PM- underground Phone #: ###-#### ok cover under ground conduit to out building