Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberELE08-02230
StatusFinaled
Name LINDA WRIGHT
Site Address 2310 N SIESTA WAY
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/27/200911/27/200911/27/2009PPASS
DetailsDoug A Poedy
Linda - late afternoon please - also please call 1/2 hr prior Phone #: ###-####. Ok final.
DOC - Permit Finaled11/27/200911/27/200911/27/2009PPASS
DetailsDoug A Poedy
Conference9/18/20099/18/20099/18/2009PDONE
DetailsJack Frank
ok
Electrical Rough-In4/10/20094/13/20094/13/2009APART
DetailsJack Frank
Linda- first thing AM if possible Phone #: ###-#### ok
Permanent Service4/13/20094/13/20094/13/2009APASS
DetailsJack Frank
Linda- first thing AM if possible Phone #: ###-#### p/s u/g rec. ok
Permanent Service2/5/20092/5/20092/5/2009PFAIL
DetailsJack Frank
linda Note: please call 1/2 hr prior to inspection to meet with Phone #: ###-####
corr. net owner300.4 shall provide bushings for #4 or larger where it enters panel, 312.5 needs plastic conn. for GEC that enters back of panel, shall use #1 alum SER , or install 90 amp max breaker for #2 alum SER, 250.94 needs grd for other services, phone & catv
Conference12/23/200812/23/200812/23/2008PPART
DetailsJack Frank
linda Phone #: ###-#### owner called I answered his ? over the phone
Electrical Rough-In12/3/200812/3/200812/3/2008PPASS
DetailsBob Reichert
linda - cover of uffer ground Phone #: ###-#### ok to cover concrete encased electrode
Electrical Rough-In11/26/200811/26/200811/26/2008PPASS
DetailsBob Reichert
Linda late as possible Phone #: ###-#### ric ok for basement and upstairs room, ok to pour concrete encased electrode
Electrical Rough-In10/15/200810/16/200810/16/2008AFAIL
DetailsJack Frank
bryan Note: if possible first in the morning Phone #: ###-#### corr met owner
make-up not done, needs concrete encased electrode, at footing 20ft #4 copper, address both subpanels, T310.15(B)(6) shall install correct size wire for 100 amp ,or use smaller size breaker , 250.148 shall grd metal boxes
Conference10/13/200810/16/200810/16/2008ACANC
DetailsJack Frank
bryan Phone #: ###-####
Conference8/15/20088/15/20088/15/2008PDONE
DetailsJack Frank
Linda Phone #: ###-#### ok
Conference8/11/20088/12/20088/12/2008ADONE
DetailsJack Frank
linda Note: please if possible first thing in morning Phone #: ###-#### talked with owner told her some NEC requirements for job and to get books on home wiring