Final | 1/12/2009 | 1/13/2009 | 1/13/2009 | A | PASS |
Jack Frank
|
|
|
Lock Box Code 7034 Thanks Dan Phone #: ###-#### Internet Inspection Request from: Dan Rohl survey 210.52(C) outlet for countertop right of refer ok
|
Final | 10/7/2008 | 10/7/2008 | 10/7/2008 | P | CANC |
Bob Reichert
|
|
|
dan Phone #: ###-#### wrong type request, see ri and p/s, no esc this project
|
Rough-In Permanent Service | 10/7/2008 | 10/7/2008 | 10/7/2008 | P | PASS |
Bob Reichert
|
|
|
dan Phone #: ###-#### corrections made, ri ok, p/s o/h rec ok, no esc this project
|
Rough-In Permanent Service | 10/2/2008 | 10/2/2008 | 10/2/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Rohl called, left correction notice, NEC 250.52(A)(1) shall use incoming water pipe as a grounding electrode, 230.24(A) service conductors shall be 8' above roof surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.30 shall secure nm cable within 12" of box (sub-panel), 210.52(A)(1) shall space receptacles such that no point along floor line is more than 6' from a receptacle outlet, BCC shall change room count to 15 on permit, no esc this project
|