Final | 7/10/2009 | 7/10/2009 | 7/10/2009 | A | PASS |
Bob Reichert
|
|
|
i think we are ready andy is on site this morning if you can go by and check it out thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to final, signed occupancy card, no esc this project
|
Electrical Rough-In | 5/8/2009 | 5/8/2009 | 5/8/2009 | P | PASS |
Jack Frank
|
|
|
This for the final ceilings cover two rooms on the east the large ones with can lights and soffits. Also cover on utility shed wiring east parking lot. Andy has the day off so no electricians are on site so call me with any questions or concerns. Thanks Don Phone #: ###-#### Internet Inspection Request from: Don Lustig both east west entrances, both east rms, ceilings and shed ok
|
Electrical Rough-In | 4/28/2009 | 4/28/2009 | 4/28/2009 | P | PART |
Mike Kinnear
|
|
|
ceiling cover side classrooms coordinate with andy on site thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig ok cover hard lid ceilings except for class rms.
|
Electrical Rough-In | 4/23/2009 | 4/23/2009 | 4/23/2009 | P | PASS |
Jack Frank
|
|
|
andy - for the rostrom cover Phone #: ###-#### ok
|
Permanent Service | 4/16/2009 | 4/16/2009 | 4/16/2009 | A | PASS |
Jack Frank
|
|
|
Panel M ready Main on North of church Phone #: ###-#### Internet Inspection Request from: Don Lustig p/s u/g new ok
|
Permanent Service | 4/14/2009 | 4/14/2009 | 4/14/2009 | A | FAIL |
Jack Frank
|
|
|
Main Panel on North of building ready for power Phone #: ###-#### Internet Inspection Request from: Don Lustig corr. met contr, 200.2(B) & 250.24 shall terminate GEC to grounded bus and install main bonding jumper or screw, 110.3(A) replace damaged wire at p/s (ringed the wire)300.4(G) & 352.46 provide connectors, of bushings where u/g enters bottom of service job not ready also
|
Electrical Rough-In | 3/30/2009 | 3/30/2009 | 3/30/2009 | P | PASS |
Jack Frank
|
|
|
This is for more underground cover any time you get by Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig all parking lot u/g ok
|
Electrical Rough-In | 3/27/2009 | 3/27/2009 | 3/27/2009 | P | PART |
Jack Frank
|
|
|
More parking lot underground. Phone #: ###-#### Internet Inspection Request from: Don Lustig all norht and east parking lot lights ok
|
Electrical Rough-In | 3/27/2009 | 3/27/2009 | 3/27/2009 | A | PART |
Jack Frank
|
|
|
This is for the chapel and cultrual hall wall and ceiling RI, Also for parking lot underground. Phone #: ###-#### Internet Inspection Request from: Don Lustig ok anop
|
Electrical Rough-In | 3/9/2009 | 3/9/2009 | 3/9/2009 | P | CANC |
Jack Frank
|
|
|
Andy Phone #: ###-#### see added AM r/i
|
Electrical Rough-In | 3/9/2009 | 3/9/2009 | 3/9/2009 | A | PART |
Jack Frank
|
|
|
Andy Phone #: ###-#### walls and hard ceilings anop
|
Electrical Rough-In | 2/25/2009 | 2/25/2009 | 2/25/2009 | A | CANC |
Jack Frank
|
|
|
This is for part RI on the Shear Walls so the frammer can continue his framing. Andy on site will show what walls. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig anop
|
Electrical Rough-In | 2/6/2009 | 2/6/2009 | 2/6/2009 | P | PART |
Jack Frank
|
|
|
this is for the mezzenne ceiling cover call Andy on site at ###-#### for walk thru Phone #: ###-#### Internet Inspection Request from: Don Lustig walls and ceilings ok anop
|
ELE-Aging Inspection | 1/20/2009 | 1/20/2009 | 1/20/2009 | | PART |
Jack Frank
|
|
|
stopped at site no electrical ready at this time wsuc
|
Electrical Rough-In | 11/20/2008 | 11/20/2008 | 11/20/2008 | P | PART |
Jack Frank
|
|
|
Pad underground ready for cover stuff under concrete Phone #: ###-#### Internet Inspection Request from: Don Lustig all u/g inside of church ok
|
Electrical Rough-In | 10/28/2008 | 10/28/2008 | 10/28/2008 | A | PART |
Jack Frank
|
|
|
If you can swing by and look at the underground we have in this morning sometime that would be great. Thanks Phone #: ###-#### Internet Inspection Request from: Don Lustig deep u/g inbuilding ok
|
Rough-In Permanent Service | 10/8/2008 | 10/8/2008 | 10/8/2008 | P | CANC |
Bob Reichert
|
|
|
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig wrong type request, see ri
|
Electrical Rough-In | 10/8/2008 | 10/8/2008 | 10/8/2008 | P | PASS |
Bob Reichert
|
|
|
ufer ground Phone #: ###-#### Internet Inspection Request from: Don Lustig ok to pour concrete encased electrode
|