Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE08-03211
StatusFinaled
Name PERRINE ELECTRIC
Site Address 906 N HARRISON BLVD
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/11/20095/12/20095/12/2009APASS
DetailsBob Reichert
Dave Phone #: ###-#### corrections made, ok to final
Final5/4/20095/4/20095/4/2009PFAIL
DetailsJack Frank
Dave Phone #: ###-#### corr posted called 334.15 protect 10/2 at W.H., 210.8(A)(7) needs gfci all recepts within 6ft od laundry sink, 410.10 needs shower trim , correct open equip grds left and right of disposal switch wet bar area
Final4/23/20094/24/20094/24/2009AFAIL
DetailsPat Lass
Dave Phone #: ###-####
contractor did not call for this inspection.
receps not tamper resistant and gfci protection required within 6 ft of sinks.
Electrical Rough-In12/11/200812/11/200812/11/2008PPASS
DetailsPat Lass
Call 30 mins prior to going for access Phone #: ###-####