Permit Information
Permit NumberELE09-00105
StatusExpired
Name JOSEPH BOND
Site Address 615 S PHILLIPPI ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection8/16/20108/16/20108/16/2010 CANC
DetailsJack Frank
DOC - Permit Expired8/16/20108/16/20108/16/2010APASS
DetailsJack Frank
no activity
ELE-Aging Inspection6/16/20106/16/20106/17/2010 CANC
DetailsJack Frank
no activity
ELE-Aging Inspection4/16/20104/16/20104/20/2010 CANC
DetailsJack Frank
Electrical Rough-In1/27/20091/27/20091/27/2009PPASS
DetailsBob Reichert
joe Phone #: ###-#### corrections made ric ok, kitchen and dining room only, no esc this project
Electrical Rough-In1/26/20091/27/20091/27/2009AFAIL
DetailsBob Reichert
after 9 please-joseph Phone #: ###-#### met owner, corrections 300.4 (A)&(D) 1/14" for edge of holes and nm cable shall be maintained, 210.52 (B)(2) circuits for outdoor recpt and light shall not be on dining room circuit, no esc this project
Electrical Rough-In1/23/20091/26/20091/26/2009AFAIL
DetailsJack Frank
joe Phone #: ###-#### met with owner, I explained NEC requirements for wall and countertop outlet spacing, box fill , 6" free length, what can be on small appliance branch circuits , owner said it was his house , and he thought he did not have to wire it to code
Electrical Rough-In1/21/20091/22/20091/22/2009ACANC
DetailsMike Kinnear
jim Note: please call 1/2 hr prior to inspection Phone #: ###-#### wrong type inspection no esc permit in project.
Conference1/22/20091/22/20091/22/2009ADONE
DetailsMike Kinnear
jim Note: please call 1/2 hr prior to inspection Phone #: ###-#### conf with father inlaw advised as much as i could. the owner needs to get appointment with bob for another conf.