Final | 6/19/2009 | 6/19/2009 | 6/19/2009 | P | PASS |
Jack Frank
|
|
|
Skip Phone #: ###-#### ok card signed
|
Final | 6/12/2009 | 6/12/2009 | 6/12/2009 | P | PART |
Jack Frank
|
|
|
Tim Phone #: ###-#### t/o ok still needs labels 210.5
|
Final | 6/9/2009 | 6/10/2009 | 6/12/2009 | A | NR |
Jack Frank
|
|
|
tim Phone #: ###-#### called needsID of more than one voltage present 210.5 corner grded delta grounded conductor shall be white or gray 200.6 bonding for xformer secondary side min #8 250.66
|
Electrical Rough-In | 6/3/2009 | 6/3/2009 | 6/3/2009 | P | PART |
Jack Frank
|
|
|
field evaluation for refer units ok
|
Conference | 6/3/2009 | 6/3/2009 | 6/3/2009 | P | DONE |
Jack Frank
|
|
|
needs grding for xformers and p/s load side xformers
|
Electrical Rough-In | 6/2/2009 | 6/3/2009 | 6/3/2009 | A | PART |
Jack Frank
|
|
|
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae grd for xformers, p/s rated disconnect secondary side called
|
Conference | 5/19/2009 | 5/19/2009 | 5/19/2009 | A | DONE |
Jack Frank
|
|
|
conference with UL and contr about refer units
|
Permanent Service | 4/27/2009 | 4/28/2009 | 4/28/2009 | A | PASS |
Mike Kinnear
|
|
|
tim Phone #: ###-#### p/s u/g reconnect ok survey needs factory bonding jumper in main panel
|
Permanent Service | 4/22/2009 | 4/23/2009 | 4/23/2009 | A | NR |
Mike Kinnear
|
|
|
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae t/w tim job not ready all disconnects need to be grouped
|
Conference | 4/20/2009 | 4/20/2009 | 4/20/2009 | P | DONE |
Mike Kinnear
|
|
|
Tim Phone #: ###-#### ok conf. regarding all electrical equipment which needs to be listed & labled
|
Electrical Rough-In | 4/15/2009 | 4/15/2009 | 4/15/2009 | P | PART |
Jack Frank
|
|
|
Contact: Tim Watkins Phone #: ###-#### Internet Inspection Request from: Melissa Kaae r/i ok 1 wall downstairs, corr posted to BLD09-00326, no violations retained, cord fed highbay fixtures shall meet NEC 410.62(C)(1), label and listing for portable freezer units
|