Temporary Service | 7/23/2009 | 7/24/2009 | 7/24/2009 | A | PASS |
Jack Frank
|
|
|
Please provide temp power pole inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean t/s u/g new ok
|
Temporary Service | 7/21/2009 | 7/22/2009 | 7/22/2009 | A | FAIL |
Bob Reichert
|
|
|
Please provide termpory power pole inspection Phone #: ###-#### Internet Inspection Request from: Spencer Mclean met electrician, gave correction notice, NEC 406.8(B)(1) receptacles shall be rated weather resistant, 310.16 shall provide minimum 100A use type service conductors, BCC shall provide job id stickers, fee due, no esc this project
|