Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE09-01826
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 200 E GOWEN RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Electrical work as required for new building - service, branch circuit and lighting--9-8-10-split out permit final cert of value $52,845 BAS
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/9/20104/9/20104/9/2010PPASS
DetailsDoug A Poedy
Inspection requested from web by: Scott Campbell Phone #: ###-####
DOC - Permit Finaled4/9/20104/9/20104/9/2010PPASS
DetailsDoug A Poedy
Final4/7/20104/8/20104/8/2010AFAIL
DetailsBob Reichert
Inspection requested from web by: Scott Campbell Phone #: ###-#### called, left correction notice, NEC 230.2)E), 225.37 shall identify services, 406.8 shall install listed wr type receptacles and in-use covers for outdoor receptacles, 210.8(B)(5) receptacles within 6' of sink shall be gfci protected, 406.4 receptacles shall be securely mounted, 406.4(D) receptacle face shall be flush with or project from faceplate NOTE: corrections shall be made within 5 working days or further action will be taken such as removal of power
Electrical Rough-In3/18/20103/19/20103/19/2010APART
DetailsBob Reichert
For Temporary Occupancy - New Shed Inspection requested from web by: Scott Campbell Phone #: ###-#### t/o ok for 4.4A, 5, & 6 only, signed card with correction to affix service disconnect stickers to each service
Electrical Rough-In1/19/20101/19/20101/19/2010PPASS
DetailsBob Reichert
Steve Phone #: ###-#### called, corrections made, ric ok
Electrical Rough-In1/13/20101/14/20101/14/2010PFAIL
DetailsBob Reichert
Contact is John Dillon Phone #: ###-#### Internet Inspection Request from: Scott Campbell called contractor, left correction notice, NEC 225.36 disconnecting means shall be suitable for service equipment at each building, 348.30,330.30 fmc and mc shall be securely supported within 12" of box, 250.86 shall ground metal boxes,300.4(A)&(D) edge of bored holes and mc cables shall be 1 1/4" from edge of framing member,250.32 shall provide disconnecting means inside or outside of building served per 225.31, 250.32(B) grounded conductor shall not connect to equipment grounding conductor, 110.12(A) shall close unused openings
Final12/10/200912/11/200912/11/2009APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Scott Campbell part final ok, called contractror to tighten receptacles, provide gfci for drinking fountains and refrigerator, signed t/o card
Electrical Rough-In11/20/200911/20/200911/20/2009PPASS
DetailsBob Reichert
Contact: John Dillon Phone #: ###-#### Internet Inspection Request from: Randy Vail pole bases ok to pour
Electrical Rough-In11/9/200911/9/200911/9/2009PPART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
Electrical Rough-In11/6/200911/6/200911/6/2009PPART
DetailsBob Reichert
Cover Inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail u/g ok 2nd building to east of main building mark plans next inspection, electrician not on site with plans
Electrical Rough-In11/4/200911/4/200911/4/2009PPART
DetailsBob Reichert
u/g ok to cover anop
Electrical Rough-In11/3/200911/4/200911/4/2009PCANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail
Electrical Rough-In10/29/200910/30/200910/30/2009PPART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
Electrical Rough-In10/28/200910/28/200910/28/2009PPART
DetailsMike Kinnear
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok cover under ground conduct anop
Electrical Rough-In10/26/200910/27/200910/27/2009APART
DetailsBob Reichert
underground inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail u/g ok to cover anop
Electrical Rough-In10/26/200910/26/200910/26/2009PCANC
DetailsBob Reichert
Underground inspection Phone #: ###-#### Internet Inspection Request from: Randy Vail Inspection cancelled from web by: Randy Vail
Final10/22/200910/23/200910/23/2009ACANC
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail wrong type request, see ri
Electrical Rough-In10/23/200910/23/200910/23/2009APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
Electrical Rough-In10/21/200910/22/200910/22/2009APART
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop, told to provide service at each building along with electrodes
Electrical Rough-In10/14/200910/15/200910/15/2009PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Randy Vail offices only ok to cover
Permanent Service9/29/20099/30/20099/30/2009APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 9/29/2009 at 12:34:34 PM. Contact: ###-####. p/s u/g n ok