Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE10-01134
StatusFinaled
Name COLT MEHLER
Site Address 1322 E FRANKLIN ST
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/1/201011/2/201011/2/2010APASS
DetailsDaryl DeGrange
Colt Phone #: ###-#### ok final
Rough-In Permanent Service6/21/20106/21/20106/21/2010PPASS
DetailsBob Reichert
Colt Phone #: ###-#### corrections made ric ok, p/s to house from exsisting service, u/g n ok
Electrical Rough-In6/18/20106/18/20106/18/2010PFAIL
DetailsBob Reichert
Colt Phone #: ###-#### called, bad number, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member, 210.52 shall install receptacle within 6' of doors (rear), 312.5 all conductors entering enclosure shall have abrasion protection, 334.23 shall protect cables within 6' of attic access, 250.86 shall ground metal boxes, 334.30 shall secure nm cable within 12" of termination at panel,110.3(B) listed equipment shall be installed per instructions (clamps at panel),BCC shall wire all boxes and provide make-up, NOTE: corrections shall be made within 5 working days or further action will be taken
Electrical Rough-In6/11/20106/11/20106/11/2010PPASS
DetailsBob Reichert
Underground trench inspection please-colt Phone #: ###-#### ok to cover u/g house to garage
Conference5/24/20105/24/20105/24/2010PDONE
DetailsBob Reichert
Colt Phone #: ###-#### talked about wiring and upgrading service