Permit Information
Permit NumberELE10-01328
StatusFinaled
Name BENCHMARK ELECTRIC CO
Site Address 5190 E SAWMILL WAY
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/19/20108/20/20108/20/2010APASS
DetailsDoug A Poedy
ACCESS THRU THE GARAGE CODE IS 2010. Phone #: ###-#### >> Inspection requested via web by David Oliver
DOC - Permit Finaled8/20/20108/20/20108/20/2010PPASS
DetailsDoug A Poedy
Permanent Service7/20/20107/20/20107/20/2010PPASS
DetailsDoug A Poedy
P/S U/G Connect ok.
Final6/17/20106/18/20106/18/2010ACANC
DetailsDoug A Poedy
Inspection requested from web by: David Oliver
Electrical Rough-In6/18/20106/18/20106/18/2010APASS
DetailsDoug A Poedy
Inspection requested from web by: David Oliver
Electrical Rough-In6/16/20106/16/20106/16/2010PFAIL
DetailsBob Reichert
Dustin Croft is our contact for the site. Inspection requested from web by: David Oliver Phone #: ###-#### called, left correction notice, NEC 334.23, shall protect cable within 6' of attic access, 210.52 shall provide receptacle in 2' wall by stairs, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 in combustible material, boxes shall be flush with finished surface, 210.52(E)(1) shall install receptacle at back of dwelling, BCC shall provide minimum 15"x20" access hole to jetted tub per instructions, NOTE corrections shall be made within 5 working days or further action will be taken