Final | 2/7/2011 | 2/8/2011 | 2/7/2011 | A | PASS |
Daryl DeGrange
|
|
|
Am inspection. Contact is mike his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates final ok
|
Final | 1/31/2011 | 2/1/2011 | 2/1/2011 | A | FAIL |
Daryl DeGrange
|
|
|
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates NEC. 210.8 (B) (2) All kitchen 15 and 20 ampere receptacles shall hae ground fault circuit-interrupter protection for personnel. NEC. 314.22 Surface Extension (Box extension) NEC. 314.25 Each box shall have a cover, faceplate NEC.408.4 Circuit Directory or circuit indentification. NEC. 408.7 Panel cover-unused openings for circuit breakers and switches shall be closed using identified closures.
|
Final | 1/28/2011 | 2/1/2011 | 1/31/2011 | A | CANC |
Daryl DeGrange
|
|
|
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Final | 1/27/2011 | 1/31/2011 | 1/28/2011 | A | CANC |
Daryl DeGrange
|
|
|
contact is Nick his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Final | 1/27/2011 | 1/28/2011 | 1/27/2011 | A | CANC |
Daryl DeGrange
|
|
|
Contact is Nick, his cell no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 1/19/2011 | 1/19/2011 | 1/19/2011 | P | PASS |
Daryl DeGrange
|
|
|
We need a final on the Kitchen and a ceiling inspection. The contact is Nick his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates ri ok ceiling in entry-assembly hall. need grounding conductor for water heater booster & secure junction box
|
Electrical Rough-In | 1/18/2011 | 1/20/2011 | 1/19/2011 | A | CANC |
Daryl DeGrange
|
|
|
We would like a ceiling inspection. Also Kitchen fianled. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates Inspection cancelled from web by: Shawna Gates
|
Electrical Rough-In | 1/7/2011 | 1/10/2011 | 1/10/2011 | A | PASS |
Daryl DeGrange
|
|
|
Ceiling Inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates kitchen ceiling only ri ok
|
Electrical Rough-In | 12/17/2010 | 12/20/2010 | 12/20/2010 | A | PART |
Bob Reichert
|
|
|
Ceiling inspection, 1st floor. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates soffits and walls ok
|
Final | 10/20/2010 | 10/21/2010 | 10/21/2010 | A | PART |
Doug A Poedy
|
|
|
This is a Final for basement only so they can occupy. Please don''t final entire permit out. Please call Mike at ###-#### if you have questions. Phone #: ###-#### >> Inspection requested via web by Shawna Gates
|
Electrical Rough-In | 10/19/2010 | 10/19/2010 | 10/19/2010 | P | PASS |
Bob Reichert
|
|
|
Nick is the onsite contact and his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates 5th floor walls and ceilings ok cover
|
Electrical Rough-In | 10/15/2010 | 10/18/2010 | 10/18/2010 | A | PASS |
Bob Reichert
|
|
|
Ceiling Inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement ceiling only ok, corrections made
|
Electrical Rough-In | 10/12/2010 | 10/13/2010 | 10/13/2010 | A | FAIL |
Bob Reichert
|
|
|
Ceiling inspection. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates met contractor, left correction notice, BCC no violations shall be retained, NEC 358.30(A) emt shall be supported within 3' of box, 348.30 fmc shall be supported within 12" of box and every 4 1/2'
|
Permanent Service | 9/16/2010 | 9/17/2010 | 9/17/2010 | P | PASS |
Bob Reichert
|
|
|
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates p/s u/g rec ok
|
Electrical Rough-In | 9/3/2010 | 9/3/2010 | 9/3/2010 | P | PASS |
Bob Reichert
|
|
|
Bathroom wall rough in. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates correction made, prints put panel in separate room, ri ok coset walls
|
Electrical Rough-In | 9/1/2010 | 9/2/2010 | 9/2/2010 | A | FAIL |
Bob Reichert
|
|
|
Wall rough in bathroom. Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates called, left correction notice, NEC240.32 enclosures for overcurrent devices in damp locations shall comply with 312.2, BCC 4-05-31(A) panels shall not be installed in shower rooms,4-05-32 no violations shall be retained, NOTE: corrections sjhall be made within 10 working days
|
Electrical Rough-In | 8/31/2010 | 9/1/2010 | 9/1/2010 | A | PASS |
Bob Reichert
|
|
|
Chris is the onsite contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates stairwell ceilings and 2nd floor walls only ok to cover- fire alarm not approved yet, panel in bathroom, NEC 240.32 refers to 312.5
|
Conference | 8/11/2010 | 8/11/2010 | 8/12/2010 | A | DONE |
Doug A Poedy
|
|
|
Doug, this is for 8:00 am meeting we talked about regarding service, mike ###-####
|
Conference | 8/11/2010 | 8/11/2010 | 8/12/2010 | A | DONE |
Bob Reichert
|
|
|
mike, ###-#### reviewed service and requirements, 414 will check with people who stickered gear
|
Conference | 7/23/2010 | 7/27/2010 | 7/27/2010 | A | DONE |
Bob Reichert
|
|
|
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates talked about field evaluation for service and adding new disconnect
|
Electrical Rough-In | 7/27/2010 | 7/27/2010 | 7/27/2010 | A | PASS |
Bob Reichert
|
|
|
This conference has been scheduled for 8:00am. Nick is the contact his no. is ###-####. Thank you. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement closet walls only ok to cover
|
Conference | 7/15/2010 | 7/16/2010 | 7/16/2010 | A | DONE |
Bob Reichert
|
|
|
8:00 am conf. call scheduled with Bob. Phone #: ###-#### >> Inspection requested via web by Shawna Gates reviewed service and options to bring up to code for project
|
Electrical Rough-In | 7/13/2010 | 7/14/2010 | 7/14/2010 | A | PASS |
Bob Reichert
|
|
|
Nick is the contract his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates basement walls only ok, service can't be changed because of too many disconnects without main, also ampacity of bus would be exceeded, several other violations regarding foreign piping over electrical gear, and remote service panel not correctly wired, shall meet requirements of NEC article 230, part V.
|